Cleaning Heat Exchanger and Venting System

— The heat exchanger and venting system should be
checked each year by a qualified dealer. If necessary,
the following procedures should be performed:

1. Make sure that all utilities are turned off upstream

of the furnace (both gas and electrical supplies),

2. Remove burner covers, manifold assembly with

burners, vent connectors and draft hood.

3. Clean flue box, flue ways, burner box and burners

with brush and/or vacuum cleaner.

4. After cleaning, check pilot for proper position.

Replace all parts.

5. Turn on gas and electrical supplies. Test for leaks

using soap and water solution.

A

CAUTION

Never use an open flame when testing for gas
leaks. Use a soap and water solution.

6. Check for proper operation of all controls.

Table 7 — Trouble Analysis Chart for Standing Pilot Models

A

WARNING

Turn off gas and electrical supplies to furnace before servicing. (Unless specific
test requires gas and electrical supplies )

SYMPTOM AND PROBABLE CAUSE

REMEDY

BURNERS WILL NOT IGNITE
1 Pilot light out

1 Relight pilot If pilot does not remain lit, replace

thermocouple

2

No 115-v

power to

furnace

2. Connect to power supply. Check fuse, wiring or circuit

breaker.

3 No 24-v power to control circuit

3. Check transformer; replace.

4. Miswired or loose connections

4 Check all wiring and wirenut connections.

5. No gas at main burners

5 Check to see if main valve is operating Look for loose or

broken wiring connections If no deficiency is found, replace
valve assembly.

6 Flame probe or connecting lead is shorted or open

6, Correct electrical shorting or open circuit

INADEQUATE HEATING
1 Furnace undersized for application

1 Replace with proper size furnace

2 Gas input to furnace too low

2. Check gas pressure at manifold. Clock gas meter for input

If too low, increase manifold pressure, or replace with correct

orifices.

3 Limit switch cycles main burners

3 OFF setting of fan control set too high; reset.

Dirty air filters; clean and reinstall.

Blower speed too low; use faster speed tap

Registers closed, restricted ductwork, open or remove
restriction

Check heat anticipator setting on thermostat, readjust.

ALDEHYDE ODORS (CO), SOOTING FLAME,

FLOATING FLAME
1 Incomplete combustion — poor flame characteristics

1 Air shutter on burners closed, adjust to soft, blue flame.

Check all screws aroundflueoutletsand burner compartment,
tighten

Lack of combustion air, see Installation section

Cracked heat exchanger; replace

Overfired furnace; reduce input or change orifices.

Check vent for restriction; clean as required

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.

Bookp |4

PC101

Catalog No 535-834

PrintedinUSA

Form 58ED.PB-1SI

Pg16

6-85

Replaces: 58PB-1 SI

For replacement items use Carrier Specified Parts.

Tab I6al8a

Advertising
This manual is related to the following products: