58ed,pb horizontal gas-fired furnaces, Warning, Symptom and probable cause remedy – Carrier 580PB User Manual

Page 17

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

Advertising
background image

HEATING & COOLING

58ED,PB

Horizontal Gas-Fired Furnaces

Table 8 — Trouble Analysis Chart for Electronic ignition Modeis

A

WARNING

Turn off gas and electrical supplies to furnace before servicing (Unless specific
test requires gas and electrical supplies.)

SYMPTOM AND PROBABLE CAUSE

REMEDY

PILOT WILL NOT LIGHT
1 No spark at electrode

1 Check spark gap, refer to Start-Up and Adjustment section

Check if Induced draft motor is operating If not, check power
to motor

Check for any blockage in flue venting system and chimney,
thereby preventing pressure switch from closing Unblock

if necessary

Check moisture or dirt accumulation on electrode ceramic,
clean ceramic with cloth

Cracked ceramic, replace pilot electrode assembly

Check for loose or broken wiring at and between electronic
control box and electrode. Replace wire as necessary

Check fuse or circuit breaker for 115-v supply to furnace

Check 24 v input to electronic control box If you read 24 v,
and above steps have been completed, replace electronic

control box assembly

Check pressure switch and tube assembly for any blockage
that prevents pressure switch from operating

Check continuity to determine if pressure switch has
disengaged

2 Spark shorting out to main burner

2 Realign electrode tip away from main burner but maintain

spark gap to pilot burner as noted above

3. No gas at pilot burner

3 Check to see if pilot valve is opening Look for loose or broken

wiring connections If no deficiency is found, replace valve
assembly

BURNERS WILL NOT IGNITE
1 No 115-v power to furnace

1 Connect to power supply Check fuse, wiring or circuit

breaker

2. No 24-v power to control circuit

2 Check transformer; replace

3. Miswired or loose connections

3 Check all wiring and wirenut connections

4 No gas at main burners

4 Check to see if main valve is operating. Look for loose or

broken wiring connections If no deficiency is found, replace
valve assembly

5 Flame probe or connecting lead is shorted or open

5. Correct electrical shorting or open circuit

INADEQUATE HEATING
1. Furnace undersized for application

1 Replace with proper size furnace

2 Gas input to furnace too low

2 Check gas pressure at manifold Clock gas meter for input.

If too low, increase manifold pressure, or replace with correct

orifices

3 Limit switch cycles main burners

3 OFF setting of fan control set too high, reset

Dirty air filters, clean and reinstall.

Blower speed too low, use faster speed tap

Registers closed, restricted ductwork, open or remove
restriction.

Check heat anticipator setting on thermostat; readjust

ALDEHYDE ODORS (CO), SOOTING FLAME,
FLOATING FLAME

1 Incomplete combustion — poor flame characteristics

1 Air shutter on burners closed, adjust to soft, blue flame

Check all screws around flue outlets and burner compart­

ment; tighten

Lack of combustion air, see Installation section

Cracked heat exchanger, replace

Overfired furnace; reduce input or change orifices

Check vent for restriction; clean as required

Book|1 [4

PC101

Catalog No 535-834

PrintedinUSA

Form 58ED,PB-1SI

Pg17

6-85

Replaces: 58PB-1 SI

>%