QUIETPACT“ 75D Recreational Vehicle Generator

♦ 2.T.4 GENERATOR RESTRAINT__________________

Use four 3/8"-16 hardened steel bolts (Grade 5) to fas­
ten the generator to the supporting frame or the sup­
port tubing. These bolts must pass through (a) the gen­
erator mounting base, (b) the compartment floor (if a

compartment is used) and (c) the supporting frame­

work (Figure 2.2). All bolts must be long enough so that
when tight, are engaged at least 3/8” of an inch [9.5 mil­

limeters]. Refer to Section 2.2 for the location of the
generator mounting holes.

Figure 2.2

-

Typical Generator Restraint

Figure 2.3

-

Typical Compartment Construction

METAL LINED

t/2 INCH THICK

2.2

GENERATOR COMPARTMENTS

Whether the generator set is being installed inside a

compartment specifically manufactured to house a gen­
erator or inside a compartment that the installer con­
structs, the compartment MUST meet certain specifi­
cations as outlined in the following sections:

• 2.2.T COMPARTMENT CONSTRUCTION

* •

The generator compartment should be either

constructed of, or lined with, 26-gauge galva­
nized steel.

NOTE:

Aluminum

is

NOT

an

acceptable

alternative

to

galvanized

steel

due

to

aluminum’s

low

melting point.

• If the compartment is lined with galvanized steel, it

may be constructed of any material. Generac rec­
ommends that the compartment be constructed of

1/2-inch thick plywood (not strandboard), with the

floor made of a double thickness of 1/2-inch ply­
wood with the grain of the wood at cross section

for added strength (Figure 2.3).

• If constructing a compartment, line the exterior

(underside) of the compartment floor with 26-

gauge galvanized steel.

• All seams, splices and joints of the compartment

walls (unless vapor tight by design) should
be caulked to prevent poisonous, flammable or
explosive vapors from entering the vehicle interior.

NOTE:

Caulking must be done so that the caulking materi­
al will stay in place permanently. Pressing such

materials as putty tape onto joints and seams is NOT
acceptable. A high quality silicone rubber base
sealant is recommended.

• Holes and openings made in the compartment

walls to allow for the passage of electrical conduit,
conductors, hoses, cables, etc., into the vehicle liv­
ing area must be sealed vapor tight with silicone

rubber base sealant.

• If flexible metal conduit is used, it must be sealed

internally at the end where it terminates inside the
compartment’s electrical junction box.

NOTE:

Flexible metal conduit, due to its unique con­
struction, is NOT vapor tight along its entire

length.