Acoustics, Compartment floor cutouts – Generac Power Systems 00862-1 User Manual

Page 20

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

Advertising
background image

ACOUSTICS

For additional noise abatement the installer may wish

to consider the following:

• Using special sound insulating materials.

• Construction of a special noise abatement compartment.

IMPORTANT: ANY METHOD USED TO REDUCE
NOISE MUST NOT ADVERSELY AFFECT THE
FLOW OF COOLING AND VENTILATING AIR INTO

OR OUT OF THE COMPARTMENT.

In addition to the effective use of sound insulating

materials, construction of a special noise abatement
compartment might be considered to reduce noise
levels. Such a compartment might be constructed as
follows (Figure 20):

• Use 5/8-inch thick or 3/4-inch thick plywood in the com­

partment.

• Construct the compartment floor of a double thickness of

5/8-inch or 3/4-inch plywood.

• Line the compartment interior walls and floor, as well as

the underside of the floor, with 26-gauge galvanized steel.

• Vapor seal all compartment seams and joints.

• Over the galvanized steel lining, install a selected combi­

nation of acoustical materials as mentioned in “Sound

Insulating Materials.”

DANGER: Do not install any insulation or other
absorbent materials on the interior or underside of

the compartment floor.

Seal all compartment door edges to prevent noise leak­

age around the door perimeter.

Line the compartment door interior (except for air open­

ings) with suitable, fire proof sound insulation (such as 1-

inch thick fiberglass with a 2-pound density).

Figure 20 — Typical Noise Abatement

COMPARTMENT FLOOR CUTOUTS

You must provide openings in the generator compart­
ment for the following items (Figure 21):

• Engine exhaust and cooling air outlets

• Generator cooling air inlet

• Four holes for passage of generator mounting bolts. See

“Generator Restraint” on Page 16.

DANGER: Fuel lines and exhaust piping must not

penetrate into vehicle living area.

— 18 —

Advertising