Figure 25 — Air Inlet Using Ductwork

Figure 26 — Air Inlet in Vehicle Skirt

COMPENSATING FOR

RESTRICTIONS

Such materials as screening, louvers, or expanded
metal can restrict the free flow of air. Compensate for

this restriction by making the actual air opening pro­

portionately larger.

Some materials may offer only a 60 percent “free air
inlet area.” Other more efficient materials may provide
up to a 90 percent free air inlet area. The percentage
of free air inlet opening is usually available from the
material supplier or manufacturer.

TO

DETERMINE

THE

ACTUAL

AIR

INLET

OPEN­

ING SIZE REQUIRED, DIVIDE 75 SQUARE INCHES
BY THE PERCENTAGE OF FREE AIR INLET AREA
FOR THE MATERIAL YOU WILL USE.

For example:

If you plan to use screening with an

80% free air inlet area, divide 75 by 0.8, which results
in 94 square inches. Minimum actual size of air inlet
opening in this case is 94 square inches.

TESTING THE INSTALLATION

Generac recommends testing the installation to be
sure adequate cooling air flow is available to the unit
before placing the unit into service. If the unit shows
signs of overheating, you will need to enlarge the air
openings. Never place a unit into service until
absolutely certain that cooling and ventilation is ade­
quate.

IMPORTANT; YOU MUST TEST THE INSTALLA­

TION ESPECIALLY IF YOU BRING IN AIR FROM

BELOW THE GENERATOR SET.

— 21 —