Hardware Installation

Begin the installation by mounting the cabinet in a dry protected area with access to unswitched AC power.
Install Hardware in the sequence indicated below. Do NOT apply power until installation is complete.

NOTE: All wiring entry points are designated by arrows. All circuits are classified UL power limited except for the battery leads.

Minimum 1/4” (6.4mm) separation must be maintained at all points between power limited and non-power limited wiring and
connections.

1. Keybus Wiring

The 4-wire KEYBUS (red, black, yellow and green) is the communication connection between the control panel and all modules. The 4 KEY-
BUS terminals of all modules must be connected to the 4 KEYBUS terminals of the main control panel.

The following rules must be followed when wiring the Keybus:

•

Minimum 22 AWG wire, maximum 18 AWG (2-wire twisted pre-
ferred

•

Do NOT use shielded wire

•

Modules can be home run, connected in series or can be T-
tapped provided that the maximum wire distance from the control
panel to any module does not exceed 1,000 feet (305m)

•

No more than 3,000 feet (915m) of wire can be used in total

2. Zone Wiring

Zones can be wired for Normally Open, Normally Closed Contacts
with Single-end-of-line (SEOL) resistors or Double End-of-Line
(DEOL) resistors. Observe the following guidelines
•

For UL Listed Installations use SEOL or DEOL only.

•

Minimum 22 AWG wire, maximum 18 AWG

•

Do NOT use shielded wire

•

Wire run resistance shall not exceed 100

Ω.

Refer to the chart

below.

•

Section [001-004] Selects Zone Definition

•

Section [013] Opt [1] Selects Normally Closed or EOL resistors

•

Section [013] Opt [2] Selects Single EOL or Double EOL resis-
tors.

Zone Status

Loop Resistance
- 0

Ω (shorted wire/loop)

- 5600

Ω (contact closed)

- infinite (broken wire, open)
- 11,200

Ω (contact open)

Loop Status
Fault
Secure
Tamper
Violated

3. Bell Wiring

These terminals supply 700mA of current at 12V

DC

for commercial

installations and 11.1-12.6 V

DC

for residential installations (e.g.DSC

SD-15 WULF). To comply with NFPA 72 Temporal Three Pattern
requirements:

Program Section [013] Opt [8] ON.

The Bell output is supervised and power limited. If unused, connect a
1000

Ω resistor across Bell+ and Bell- to prevent the panel from dis-

playing a trouble. See [

✱][2].

NOTE: Bell output is current lim-
ited by 2A PTC

NOTE: Steady, Pulsed and Tem-
poral Three Pattern alarms are
supported.

CONTROL

PANEL

150’ (46m)

150’ (46m)

500’ (152m)

500’ (152m)

Normally Closed Loops - Do NOT use for UL Installations

Single End-of-Line Resistor Wiring

Double End-of-Line Resistor Wiring

OBSERVE

POLARITY

BELL/SIREN
700mA (max.)