Hardware installation – DSC POWERSERIES PC1616 User Manual

Page 2

Advertising
background image

Hardware Installation

Begin the installation by mounting the cabinet in a dry protected area with access to unswitched AC power.
Install Hardware in the sequence indicated below. Do NOT apply power until installation is complete.

NOTE: All wiring entry points are designated by arrows. All circuits are classified UL power limited except for the battery leads.

Minimum 1/4” (6.4mm) separation must be maintained at all points between power limited and non-power limited wiring and
connections.

1. Keybus Wiring

The 4-wire KEYBUS (red, black, yellow and green) is the communication connection between the control panel and all modules. The 4 KEY-
BUS terminals of all modules must be connected to the 4 KEYBUS terminals of the main control panel.

The following rules must be followed when wiring the Keybus:

Minimum 22 AWG wire, maximum 18 AWG (2-wire twisted pre-
ferred

Do NOT use shielded wire

Modules can be home run, connected in series or can be T-
tapped provided that the maximum wire distance from the control
panel to any module does not exceed 1,000 feet (305m)

No more than 3,000 feet (915m) of wire can be used in total

2. Zone Wiring

Zones can be wired for Normally Open, Normally Closed Contacts
with Single-end-of-line (SEOL) resistors or Double End-of-Line
(DEOL) resistors. Observe the following guidelines

For UL Listed Installations use SEOL or DEOL only.

Minimum 22 AWG wire, maximum 18 AWG

Do NOT use shielded wire

Wire run resistance shall not exceed 100

Ω.

Refer to the chart

below.

Section [001-004] Selects Zone Definition

Section [013] Opt [1] Selects Normally Closed or EOL resistors

Section [013] Opt [2] Selects Single EOL or Double EOL resis-
tors.

Zone Status

Loop Resistance
- 0

Ω (shorted wire/loop)

- 5600

Ω (contact closed)

- infinite (broken wire, open)
- 11,200

Ω (contact open)

Loop Status
Fault
Secure
Tamper
Violated

3. Bell Wiring

These terminals supply 700mA of current at 12V

DC

for commercial

installations and 11.1-12.6 V

DC

for residential installations (e.g.DSC

SD-15 WULF). To comply with NFPA 72 Temporal Three Pattern
requirements:

Program Section [013] Opt [8] ON.

The Bell output is supervised and power limited. If unused, connect a
1000

Ω resistor across Bell+ and Bell- to prevent the panel from dis-

playing a trouble. See [

][2].

NOTE: Bell output is current lim-
ited by 2A PTC

NOTE: Steady, Pulsed and Tem-
poral Three Pattern alarms are
supported.

CONTROL

PANEL

150’ (46m)

150’ (46m)

500’ (152m)

500’ (152m)

Normally Closed Loops - Do NOT use for UL Installations

Single End-of-Line Resistor Wiring

Double End-of-Line Resistor Wiring

OBSERVE

POLARITY

BELL/SIREN
700mA (max.)