Hardware installation (cont.), 12v / 7 ahr, 12v / 7 ahr north america only – DSC POWERSERIES PC1616 User Manual

Page 3: Warning, Important, Ua503

Advertising
background image

Hardware Installation (Cont.)

PC Board

Cabinet

Stand Off

Primary:120VAC/60Hz.
Secondary: 16.5VDC 40VA
DSCPTD 1640U
Class II Transformer

NOTE: Do not connect
transformer to receptacle
controlled by a switch

Incorrect connections may result in PTC failure or improper operation.

Inspect wiring and ensure connections are correct before applying power.

WARNING:

Incorrect connection of batteries may result in battery rupture or Fire Hazard.
Do NOT allow metal objects to connect the Positive and Negative Terminals.
Ensure that batteries are connected with correct polarity (Red to (+), Black to (-)).
Failure to comply with this may result in battery rupture and/or Fire Hazard.
All circuits are classified for UL Installations as Power Limited/Class II Power Limited
except for battery leads which are not power limited.

Do NOT route any wiring over circuit boards. Maintain at least 1"(25.4mm) separation.
A minimum of 1/4" (6.4mm) separation must be maintained at all points between
power limited wiring and all other non-power limited wiring.

1. Insert Stand off into cabinet

mounting hole in the
desired location. Snap-in-
place.

2. Position circuit board

mounting holes over
standoffs. Press firmly
on board to snap-in-place.

IMPORTANT:

a)This equipment, Alarm Controller PC1616/1832/1864 shall

be installed and used within an environment that provides the
pollution degree max 2 and overvoltages category II
NON-HAZARDOUS LOCATIONS, indoor only. The equipment is
FIXED and PERMANENTLY connected and is designed to be
installed by service persons only; [service person is defined as a
person having the appropriate technical training and experience
necessary to be aware of hazards to which that person may be
exposed in performing a task and of measures to minimize the risks
to that person or other persons.]

b)The connection to the mains supply must be made as per the local

authorities rules and regulations.
An appropriate disconnect device must be provided as part of the
building installation. Where it is not possible to rely on identification of
the neutral in the AC Mains supply the disconnecting device must

disconnect both poles simultaneously (line and neutral). The device

shall disconnect the supply during servicing.

c)The equipment enclosure must be secured to the building structure

before operation.

e)Internal wiring must be routed in a manner that prevents:

- Excessive strain on wire and on terminal connections;
- Loosening of terminal; connections;
- Damage of conductor insulation

f) Disposal of the used batteries shall be made according to the waste

recovery and recycling regulations applicable to the intended market.

g) Before servicing, DISCONNECT the telephone connection.

See corresponding Section NumberText for wiring details.

CON1

BAT+BAT-

FUSE

AC AC

16.5V

/40VA

AC

To EGND

Terminal

230 V

/50 Hz International

AC

CON1

BAT+BAT-

POWER LIMITED

NON-POWER LIMITED

DSC Model BD7-12

or equivalent

Battery

StandbyTime:

24Hrs min.

BLACK

RED

TB-2

AC AC

RED BLK YEL GRN

Z1 COM Z2 Z3 COM Z4 Z5 COM Z6 Z7 COM Z8

AUX+

BELL+

AUX-

BELL-

PGM1 PGM3

EGND

TIP

T-1

PGM2 PGM4

RING R-1

DSC

22

0

22

0

UA503

Cable Tie (not supplied) recommended

PC1864

Only

PC1864
PC1832

Only

PC1616/1832/1864

See Section 9
for ground wiring details

High Voltage. Disconnect AC Power

and telephone lines before servicing

WARNING:

High Voltage. Disconnect AC Power

and telephone lines before servicing

WARNING:

9

8

4

3

1

5

6

2

7

TB-2

AC AC

RED BLK YEL GRN

Z1 COM Z2 Z3 COM Z4 Z5 COM Z6 Z7 COM Z8

AUX+

BELL+

AUX-

BELL-

PGM1 PGM3

EGND

TIP

T-1

PGM2 PGM4

RING R-1

DSC

REV XX

22022

0

UA503

CON1

BAT+BAT-

PC-LINK

Internally Connected

AUX+ and Keybus (Red) are Internally Connected
Total current draw from Keypads, PGM Outputs and
Aux circuits must not exceed 550ma

PC1864

Only

PC1864
PC1832

Only

PC1616/1832/1864

10

12V / 7 AHr

12V / 7 AHr

North America Only

Advertising