INSTALLATION

Continued

We recommend that you install a sediment trap in

supply line as shown in Figure 20, page 16. Locate

sediment trap where it is within reach for cleaning.

Install in piping system between fuel supply and

heater. Locate sediment trap where trapped mat-

ter is not likely to freeze. A sediment trap traps

moisture and contaminants. This keeps them from

going into fireplace controls. If sediment trap is

not installed or is installed wrong, fireplace may

not run properly.

CONNECTING EQUIPMENT
SHUTOFF VALVE TO HEATER
CONTROL

Installation Items Needed
• Phillips screwdriver
• sealant (resistant to propane/LP gas, not

provided)

1. Open lower louver (see Figure 21).

NOTICE: Most building codes

do not permit concealed gas

connections. A flexible gas line

is provided to allow accessibility

from the fireplace (see Figure 21).

The flexible gas supply line con-

nection to the equipment shutoff

valve should be accessible.

2. Route flexible gas line, included, from fire-

place control to equipment shutoff valve

through side access holes in outer casing.

3. Apply pipe joint sealant lightly to male

threads of gas connector attached to flex-

ible gas line/equipment shutoff valve (see
Figure 22).

CAUTION: Avoid damage to

gas control. Hold gas control

with wrench when connecting it

to gas piping and/or fittings.

4. Check all gas connections for leaks (see

Checking Gas Connections). Feed lexible

gas line into fireplace. Make sure the entire

flexible gas line is in fireplace.

Figure 21 - Flexible Gas Line Location

O

F
F

P

ILO

T

O

N

H

I

L

O

Lower
Louver

Flexible Gas
Line

Figure 22 - Attaching Flexible Gas Line

to Equipment Shutoff Valve

Flexible Gas Line
from Fireplace
Gas Regulator
Provided With
Fireplace

To Control
Valve

Equipment
Shutoff
Valve

PROPANE/LP

To External Regulator

NATURAL GAS

To Gas Supply

CHECKING GAS CONNECTIONS

WARNING: Test all gas piping

and connections, internal and

external to unit, for leaks after

installing or servicing. Correct

all leaks at once.

WARNING: Never use an

open flame to check for a leak.

Apply a noncorrosive leak detec-

tion fluid to all joints. Bubbles

forming show a leak. Correct all

leaks at once.