1.3 Overview of NuDAM-6052

1.3.1 What is NuDAM-6052 ?

NuDAM-6052 provides 8 isolated digital input channels. Six of the input
channels are differential type and two of them are single-ended with common
ground. The isolation voltage is up to 5000 Vrms. It is suitable to use
NuDAM-6052 in industrial environment with the dangerous of high voltage
electric shock.

1.3.2 Features of NuDAM-6052

♦

8 bits isolated input

♦

5000 Vrms isolation voltage

♦

Programmable host watchdog timer for host failure protection

♦

Internal watchdog timer for device failure protection

♦

Easy programming by software

♦

Easy installation and wiring

1.3.3 Specifications of NuDAM-6052

♦

Interface

• Interface : RS-485, 2 wires

• Speed (bps) : 1200, 2400, 4800, 9600, 19.2K, 38.4K, 115.2K

(115.2K only for firmware reversion above A4.00)

♦

Input

• Channel numbers : 6 differential channels, 2 single ended

• Logical level 0 : +1V Max.

• Logical level 1: +3.5V ~ +24V

♦

Watchdog Function

• Module internal watchdog timer : 150ms

• Power failure threshold : 4.65 V