ADLINK ND-6054 User Manual
Page 69
 
Command Set
• 61
Command Set of Digital I/O Modules
Command Syntax
Module
General Commands
Set Configuration 
 
%(OldAddr)(NewAddr) 
(TypeCode)(BaudRate) 
(CheckSumFlag) 
ALL
Read Configuration
$(Addr)2
ALL
Read Module Name
$(Addr)M
ALL
Read Firmware Version
$(Addr)F
ALL
Reset Status
$(Addr)5
ALL
Functional Commands
Synchronized Sampling
#**
6050, 6052, 
6053, 6054, 
6058, 6060 
Read Synchronized Data
$(Addr)4
6050, 6052, 
6053, 6054, 
6058, 6060 
Digital Output
#(Addr)(ChannelNo) 
(OutData) 
6050, 6060, 
6063 
#(Addr)(Port)(Odata)
6056, 6058
#(Addr)(Port)(ChannelNo)
(BitData) 
6056,6058
#(Addr)T(OdataA)(OdataB
)(OdataC) 
6058
Digital Input
$(Addr)6
ALL
Set Programmable I/O Mode
$(Addr)S(IOSts)
6058
Special Commands
Read Command Leading Code 
Setting 
~(Addr)0
ALL
Change Command Leading Code 
Setting 
~(Addr)10(C1)(C2)(C3) 
(C4)(C5)(C6) 
ALL
Set Host Watchdog / Safety Value
~(Addr)2(Flag)(TimeOut) 
(SafeValue) 
ALL
Read Host WatchDog / Safe 
Value 
~(Addr)3
ALL
Change Polarity
~(Addr)CP(Status)
ALL
Read Polarity
~(Addr)CR
ALL
Host is OK
~**
ALL