Dunkirk Helix VX Vertical Laser Tube Wall Hung Stainless Steel Modulating Condensing Boiler User Manual

Page 86

Advertising
background image

86

150/200 MBH - PRIMARY LOOP EQUIVALENT LENGTH CALCULATION & PUMP SELECTION

For 150/200 MBH Boilers

(This boiler must be piped with a primary loop)

These charts are valid for piping diagrams on pages 17 & 18
Instructions:

1.

Pipe diameter determines pump size. Smaller the diameter of pipe, larger the pump. 150/200 Mbh boilers can be

piped in 3/4" , 1" or 1¼" pipe. Use charts 1-4 to determine pipe size and respective pump size.

2.

Fill in chart using the 1" section first. Then consult chart 4 for pump selection.

3.

Pump size may be decreased by decreasing equivalent length of pipe. Use larger diameter pipe as primary loop to

decrease equivalent length. Use charts 2 or 3.

Note: The figures below are based on industry average. Consult valve/fitting manufaturer for exact equivalent length or

for fittings not shown below.

Chart 1

A

B

C

Pipe Diameter

Fitting

Enter Number of

Fittings

Multiply By

Equivalent Length

A x B

1"

90° Elbow

2.5

45° Elbow

1.3

Tee-branch

5.0

Tee-through

1.7

Swing check valve

8.3

Lift check valve

50.0

Enter Total 1" straight pipe length in feet

Add up numbers in column C

Total equivalent length of Primary

Pump Factor

Chart 2

A

B

C

Pipe Diameter

Fitting

Enter Number of

Fittings

Multiply By

Equivalent Length

A x B

1¼"

(Any pipe/fitting

larger than 1¼",

count as 1¼")

90° Elbow

3.1

45° Elbow

1.7

Tee-branch

6.3

Tee-through

2.1

Swing check valve

10.4

Lift check valve

62.5

Enter Total 1¼" straight pipe length in feet

Add up numbers in column C

Total equivalent length of Primary

Multiply Total of Column C in Chart 2 by 0.35

Pump Factor