DuraVent DuraConnect User Manual

Page 10

Advertising
background image

10

using a Gas Vent Support installed under

the flashing. As an alternative to using

the Gas Vent Support, you can use a

Wall Strap if there is a roof joist nearby,

or you can field-fabricate a support-

plate that will both support the weight

and prevent lateral movement of the

vent. Do not penetrate the inner liner of

the vent. It is important that the rigid

sections of Gas Vent are properly secured

for a safe installation.

Figure 7

-When installing DuraConnect II as a

segment in a Crawl Space, rigid Type B

Gas Vent must extend a

minimum of 3” through any penetration

(wall, floor, ceiling, etc). The rigid Type B

Gas Vent must also be supported using

a Firestop Support, Gas Vent Support or

Wall Strap, in order to remove the weight

load from the DuraConnect II section.

Please refer to the full instructions for

DuraConnect II in the front part of this

document, and Type B Gas Vent (L204)

for the remainder of the installation.