Addendum – DuraVent DuraConnect User Manual

Page 9

Advertising
background image

9

SBCCI Compliance Report 9135

ICBO Evaluation Report 4895

BOCA Research Report 90-82

Patent 5,165,732

National, Standard, and Uniform

Mechanical Codes. The DuraConnect

flexible connector system has been

approved by SBCCI, BOCA and ICBO.

ADDENDUM

This is an addendum to the DuraConnect

& DuraConnect II Installation

Instructions. Please read the full

Installation Instructions for DuraConnect

& DuraConnect II in this document, as

well as the Installation Instructions for

Simpson Dura-Vent Gas Vent systems

(L204) in addition to this document.

Where the full Installation Instructions

for DuraConnect II and this addendum

differ, this addendum takes precedence.

WARNING: It is important that vents

and vent connectors be installed in

accordance with simpson dura-vent

installation nstructions. A major cause

of fire related problems with vents

and vent connectors is the failure to

install with required clearances (air

spaces) to combustible materials.

Read through all of these instructions

before beginning your installation.

Failure to install the connector as

described in these instructions will

void the manufacturers warranty

and may affect your homeowner’s

insurance and UL listing.

DuraConnect II has been approved by

Underwriters Laboratories for use as

a segment of Type B Gas vent system

for installation in conditioned and

unconditioned Attics and Crawl Spaces,

as explained in these instructions.

Please note that this applies only

to DuraConnect II (double wall flex

segment/connector) and NOT to

DuraConnect (single wall flex connector).

DuraConnect II is considered to have the

equivalent thermal properties as B-Vent

(double-wall gas vent), and can be used

where a B-Vent connector is required.

Please refer to the NFPA 54 (National

Fuel Gas Code) or the Sizing Handbook

available from Simpson Dura-Vent for

proper gas vent sizing.

The following restrictions apply to

installing DuraConnect II as a Gas Vent

Segment:

- DuraConnect II may NOT be fully

enclosed inside a chase.

- DuraConnect II may NOT penetrate or

pass through any combustible surface

(walls, ceilings, floors, orroofs, etc.).

Passing through combustible surfaces

can only be done with rigid gas vent

sections (see L204 for instructions).

- Always maintain at least 1” clearance

between DuraConnect II and

combustible materials.

- When installing DuraConnect II as a

segment in an Attic space (Fig 7), rigid

Type B Gas Vent must

penetrate at least 3” up into the Attic

before DuraConnect II can be attached.

The Type B Gas Vent

extending up into the Attic must be

secured using either a Firestop Support,

or a combination of Firestop Spacer

and Wall Strap. Also, there must be a

minimum of 3” of rigid Type B Gas Vent

extending down below roof joists. The

rigid Type B Gas Vent above the segment

of DuraConnect II must also be secured