Installation procedure – DuraVent DuraConnect User Manual

Page 6

Advertising
background image

6

of a firestop plate at the ceiling.

For multiple gas installations, such as

a furnace and hot water heater, a wide

selection of "Tees" and "Y's" are available

in single wall or double wall (B-vent).

Note: Providing the "TEE" or "Y"

connectors are attached to the Type B

gas vent in it's fully twist-lock position,

no screws are required for fastening.

However, if the branch on the "TEE" or

"Y" is angled in some desired direction,

and as a result the fitting is not in it's

fully twist-locked position, the fitting

should be fastened with one or more

sheet metal screws.

INSTALLATION PROCEDURE

Step 1. Secure Type B gas vent such that

it protrudes a minimum of 1 inch into

the room from a combustible ceiling or

wall. Use a DuraConnect round ceiling

support or wall straps.

Step 2. For a single appliance, simply

twist-lock the flex pipe directly into the

Type B gas vent. As an alternative, the

flex pipe may be attached to the branch

of a "Tee", with the tee cap installed in

the base of the tee.

Step 3. For common venting multiple

appliances, twist-lock a double wall or

single wall "TEE" or "Y" to the Type B gas

vent, then simply twist-lock the flexible

connectors into the TEE or Y fitting.

Step 4. Bend the flexible connector

into position. Avoid dips or sags, and

maintain a minimum 1/4 inch per foot

rise. When possible, use gradual "sweep"

type bends for optimum draft and flow

performance.

Step 5. Attach the flexible pipe to the

outlet of the applianceby using a Draft

Hood Connector for DuraConnect II

1"

WALL

FURNACE

B-VENT

WATER HEATER

CEILING

SDV SUPPORT

1

2

2

3

3

4

4

5

5

FURNACE ROOM,

GARAGE

1"

Figure 1

Figure 2

WATER HEATER

B-VENT

FURNACE

FLEX CONNECTOR

B-VENT