Diagram 8.9

UNION CONNECTION

DISCHARGE
PIPE

8 Mounting the boiler

SAFETY
VALVE
DISCHARGE

8080

Diagram 8.8

FITTED TO HYDRO BLOCK

SERVICE
COCKS (4)

GAS SUPPLY

SEAL

PRESSURE
GAUGE
CONNECTION

DISCHARGE
PIPE

7405

Diagram 8.7

8.5 Rear Outlet Flue Fixing

Make sure that the ductings do not slope down towards the
boiler.

Fit the air duct into the flue spigot by pulling the air duct into the
flue spigot, locating cutouts. Turn the air duct anti-clockwise to
lock into the cutouts, see diagram 8.10.

Note: It is important the correct restrictor plate is fitted or refitted,
see restrictor table.

Fit the flue connecting sleeve onto the fan, see diagram 8.11.

Fit the fan to the flue ducting, see diagram 8.11.

Fit the fan and flue collector the electrical connections and air
pressure tubes to the fan.

Refit the combustion chamber panel.

Make the outer wall weatherproof. A Flue Collar Kit Part No.
443286 is available.

8.6 Top Outlet Side or Rear Flue Fixing

Position the restrictor plate supplied in the loose items pack,
between the flue elbow and boiler , (gasket facing upwards). Fit
the flue elbow to the restrictor plate and top of the boiler using
the four screws supplied, see diagram 8.7.

Tighten the four screws of the flue elbow evenly to ensure a
good seal at the gasket.

Note: It is important the correct restrictor plate is fitted or omitted
where instructed.

For top flue outlet be sure to use the correct restrictor plate, all
restrictors are supplied with the appliance, see restrictor table.

RESTRICTOR/
GASKET

FLUE ELBOW
(REAR FLUE
SHOWN)

SECURING
SCREW (4)

PRODUCTS
PROBE

FLUE OUTLET

MAX.

USE RESTRICTOR

FLUE

PLATE MARKED

LENGTH

1. REAR

0M to 0.5M

COMP 75E/80E

0.5M-MAX

or

'F'

2. REAR

0.5M to 2.5M

COMP 75E/80E

0.5m-3.5M

or

'G'

3. TOP

0M to 2.5M

COMP 75E/80E

2.5M-MAX

or

'E'

RESTRICTOR TABLE

SEALING
WASHER (4)
(INSERT INTO
TUBING NUT)