8 mounting the boiler – Glow-worm Compact 80E User Manual
Page 19

19
221742D
7308
Diagram 8.11
FAN
FLUE
DUCTING
Diagram 8.10
FLUE
CONNECTING
SLEEVE
AIR
DUCT
FLUE
SPIGOT
TAB (2)
CUTOUT (2)
8 Mounting the boiler
7404
Diagram 8.12
7307
Diagram 8.13
7306
Diagram 8.14
FAN
FLUE
DUCTING
FLUE
CONNECTING
SLEEVE
Push
to fit
FAN
FLUE
CONNECTING
SLEEVE
SECURING
SCREW
RETAINING
LIP
FLUE
DUCTING
FLUE
CONNECTING
SLEEVE
FLUE
COLLECTOR
RETAINING
LIP
FAN
(Push up
to fit)
AIR
PRESSURE
TUBE (2)
ELECTRICAL
CONNECTIONS
7305
CLEAR
RED
Make sure that the ductings do not slope down towards the
boiler.
Remove the fan from the flue collector, secured with a screw
and retaining lip.
Fit the flue connecting sleeve onto the fan, see diagram 8.12.
Fit the fan to the flue ducting, Holding it up in position fit the flue
collector, see diagram 8.13.
Secure the fan to the flue collector with the securing screw and
retaining lip, see diagram 8.14.
Fit the electrical connections and air pressure tubes to the fan.
Refit the combustion chamber panel.
Make the outer wall weatherproof. A Flue Collar Kit Part No.
443286 is available.