INSTALLATION

- 26 -

13895

Open all hot water taps in turn and close them when water

flows. Check for water soundness of the complete domestic

water system.

The water flow rate is restricted by a restrictor factory fitted to

the boiler.

11.4 Re-pressurising System

1. Ensure that the flexible hose is connected to the double

check valve by tightening the knurled nut marked ‘E’.

2. Open the two filling taps marked ‘D’ by rotating them

through 90

O

to fill the heating system to a pressure of

1.0bar. Close the two filling taps marked ‘D’.

3. Vent all air from the system - repeat step 2 as neccessary

until the system is full and all the air has been removed.

4. To comply with the water regulations the flexible hose must

be disconnected from the double check valve - undo the

knurled nut marked ‘E’ and pull the flexible hose from the

double check valve.

11.5 Gas Supply

The gas valve is factory set for natural gas (G20) and should

need no adjustment. Turn on the gas supply at the isolation

valve, see diagram 11.1. Check the supply pressure at the

pressure test point is 20mbar.

Commissioning should only be carried out by a

competent

person approved at the time by the Health and Safety

Executive.

11.6 Initial Lighting

NOTE: Ensure that initial lighting of the appliance takes

place with the front casing door removed and the control

box lowered. Initially run the appliance pump to ensure all

air has been vented from the system (observe the

operation of the auto air vent, if possible).

The combustion for this appliance has been checked,

adjusted and preset at the factory for operation on natural

gas (G20) as defined on the appliance data label.

Do not adjust the Gas/Air ratio valve.

As an option, a chargeable boiler performance and function

service can be provided by Glow-worm Service by calling

telephone No. 01773 828100.

It is a requirement to measure and record the CO value and

CO/CO2 ratio. Guidance on measuring the values can be

documented in the Benchmark log book at the very back of this

manual.

Diagram 11.1

7. Close the Domestic Cold Water isolation valve marked

‘B’ using a screwdriver or a 3mm allen key (shown closed

in diagram).

8. Close the Central Heating Flow and Return isolation

valves marked ‘A’ using a screwdriver or a 4mm allen key

(shown closed in diagram). If the manometer kit was used,

close drain point marked ‘C’ and remove the manometer.

9. To comply with the water regulations the flexible hose

must be disconnected from the double check valve - undo

the knurled nut marked ‘E’ and pull the flexible hose from

the double check valve.

11.2 Filling the System and Boiler

1. Ensure that the flexible hose is connected to the double

check valve by tightening the knurled nut marked ‘E’.

2. Open the Central Heating Flow and Return isolation valves

marked ‘B’ using a screwdriver or a 4mm allen key - slot

in line with the axis of the isolation valve (shown closed in

diagram).

3. Open the Domestic Cold Water cock marked ‘B’ using a

screwdriver or a 3mm allen key - slot in line with the axis

of the isolation valve (shown closed in diagram).

4. Switch on the appliance, refer to diagram 11.2.

Set the Central Heating temperature and the Domestic Hot

Water temperature to OFF by pressing the MODE button

on the User Interface until it shows the appropriate symbol

°C

bar

or

°C

bar

and then pressing the - (minus) SELECTOR

button.

The display will now permanently show system pressure.

5. Open the two filling taps marked ‘D’ by rotating them

through 90

O

to fill the heating system to a pressure of

1.0bar. Close the two filling taps marked ‘D’.

6. Vent all air from the system - repeat step 5 as neccessary

until the system is full and all the air has been removed.

7. After filling is complete set the Central Heating

temperature and the Domestic Hot Water temperature

to the desired level using the MODE and + (plus)

SELECTOR buttons as described above.

8. To comply with the water regulations the flexible hose

must be disconnected from the double check valve - undo

the knurled nut marked ‘E’ and pull the flexible hose from

the double check valve.

11.3 Filling Domestic Water Circuit

Fully open any valves in the domestic water supply to the boiler.

Open the domestic water isolation valve, slot in line with the

length of the valve (shown closed in diagram).