MAINTENANCE

- 30 -

13554

Diagram 12.3

FRONT

PANEL

SECURING

SCREWS

13093

Diagram 12.2

Diagram 12.4

12776

All routine servicing requirements can be achieved by the

removal of the front panel, see diagram 12.2. Position the

control box into the service position, see diagram 12.3.

Before commencing with a service or replacement of parts.

The boiler should be isolated from the electrical and gas

supplies.

● Rotate the “throttle”(anti-clockwise to increase), to the

required CO2, refer to diagram 12.4 and the “SETTING” column

in the table.

● Exit the forced rate function, press the “mode” and “+”

buttons simultaneously, this will reset the boiler to the default

display. Now proceed to check the minimum rate adjustment.

2. Minimum Rate Check and Adjustment

● Now check the minimum gas rate CO2 setting: Press

and release the “reset” button on the controls fascia, then

immediately press and hold in either of the “+” buttons. After

approximately 5 seconds “Hi” will be displayed. Pressing the

“+” or “-” buttons will toggle between “Hi” and “Lo”. Press the

mode button when “Lo” is selected, this will force the boiler to

minimum rate and the display will flash “Lo”, indicating the boiler

is operating at minimum.

● Wait until the CO2 value is stable and check that the value is

within the range specified in table in the “check” column.

If adjustment is necessary, proceed as follows:

NOTE: Adjustment of the CO2 at minimum rate is very

coarse and should not be adjusted more than an ⅛ of

a turn at a time. Wait 1 minute to allow the appliance to

stabilise before checking or making further adjustments.

● Gradually rotate the “offset adjustment” (anti-clockwise to

decrease) to the required CO2, refer to diagram 12.4 and the

“SETTING” column in the table.

● Exit the minimum rate function, press the “mode” and “+”

buttons simultaneously, this will reset the boiler to the default

display.

3. Re-Check CO2 and check the CO/CO2

combustion ratio.

● Re-check the maximum and minimum CO2 values to ensure

that they are within the “setting” limits in the table then check

the CO/CO2 combustion ratio does not exceed the value in the

CO/CO2 column of the table. If the CO/CO2 ratio exceeds the

value in the table, a complete servicing of the appliance will be

necessary, refer to section 12.1.

If the CO2 and the CO/CO2 ratio falls within the tolerances

quoted, exit the function press the “mode” and “+” buttons

simultaneously, this will reset the boiler to the default display.

Remove the analyser probe and replace the cap on the

sampling point, replace the controls fascia, inner and front

casing panels.

IMPORTANT: Remember to replace the sample point cap on

completion of the test.

GAS RATE CHECK

Check the gas rates as described in the commissioning

section.

COMPLETION

If it is not possible to achieve the required results for either

the combustion or gas rates, it will be necessary to complete

a full service of the appliance and then repeat the combustion

check procedure. If after servicing and adjustment of the

appliance the combustion values are still unacceptable and

after further remedial work has been carried out, the appliance

must be disconnected until the CO/CO2 ratio is acceptable.

Advice can be sought from the Glow-worm Technical Helpline.

12.1 Servicing

NOTE: If the Combustion CO2, CO/CO2 ratio & Gas rate

checks did not require adjustment then it will not be necessary

to complete a full service.