Maintenance, 23 flow sensor, 24 three way valve – Glow-worm Flexicom cx User Manual

Page 44

Advertising
background image

0020107232_03 - 12/14 - Glow-worm

MAINTENANCE

- 44 -

12668

13064

Diagram 14.10

Diagram 14.11

14.23 Flow Sensor

For access, refer to section 14.1.

Refer to section 14.1 and drain the boiler hot water circuit.

Refer to diagram 14.10.

Undo the brass securing nut on the domestic cold water return

pipe.

Remove the securing clip between the hydroblock and the flow

sensor.

Remove the electrical connection to the flow sensor.

Remove the securing clip holding the brass elbow to the flow

sensor.

Partially withdraw the flow sensor to allow removal of the

electrical connection before full removal of the sensor.

Remove flow sensor.

Fit new ‘O’ rings.

After replacing the flow sensor, open the cold-water isolation

valve and slowly open a hot water tap to remove air.

Close the hot water tap and check for any leaks.

14.24 Three Way Valve

For access, refer to section 14.1.

Refer to section 14.1 and drain the boiler heating circuit and

the boiler hot water circuit.

Refer to diagram 14.11.

Undo the nut retaining the heating return isolation valve to the

fixing jig. Be careful not to lose the sealing washer.

Undo the securing nut on the underside of the fixing jig and pull

the pipe away from the three-way valve assembly.

Fully remove the three securing screws and pull the three-

way valve assembly towards the left to disengage from the

hydroblock. (Ensure that the original o-ring has not been

retained in the hydroblock.)

Fit the new three-way valve assembly.

Reassemble, refill, vent and pressurise the boiler and check for

leaks.