4 installation – Glow-worm Hideaway 80BFF User Manual

Page 15

Advertising
background image

15

221958B

4 Installation

Diagram 4.16

0886

WING NUT

SELF
TAPPING
SCREWS
(3)

Diagram 4.17

TOGGLE
LATCHES

FAN ACCESS DOOR

4.12 Flue / Boiler Connection

Remove the three self-tapping screws from the lower part of the
control box support bracket, see diagram 4.16.

Undo the wing nut that secures the top of the heat shield and
carefully hinge down control box and heat shield, see diagram
4.16.

Release the two toggle latches that secure the boiler access
door and remove, see diagram 4.17.

Remove the electrical connections from the fan by pulling the
insulation boots only.

Disconnect the two air pressure tubes from the fan taking note
of their positions.

Remove the fan assembly from the flue hood by removing the
securing screw, pull forward and lift up to release the 3 hooked
securing lugs underneath the fan, see diagram 4.18.

From the flue pack take the flue spigot,the gasket is supplied in
the fittings pack.

Connect the flue spigot and gasket to the rear flue outlet of the
boiler using the self tapping screws provided, see diagram 4.3.

IMPORTANT. With regards to the Manual Handling Operations,
1992 Regulations, the following operation, exceeds the
recommended weight for one man lift.

Place the boiler in position taking care not to damage the casing
panels.

With access to the flue system through the boiler, pull the flue
on to the spigot bayonet connection, twist anti-clockwise to lock
into position.

Take the flue duct extension from the boiler and slide on to the
fan duct until it will go no further, see diagram 4.19.

Fit fan and engage the flue duct extension into the flue duct,
secure fan, replace electrical connections and air pressure
tubes.

The polarity of the electrical connections is not important.

Make sure that the air pressure tubes are fitted as before, see
diagram 4.20 and that the fan duct engages fully into the flue
duct extension piece.

(3) SELF
TAPPING
SCREWS
(for height
adjustment
only)

"LOW"
position

"HIGH"
position

"LOW"
position

"HIGH"
position

Diagram 4.18

SECURING
LUGS