6 commissioning – Glow-worm Ultimate 30FF User Manual

Page 23

Advertising
background image

23

221518L

6 Commissioning

Diagram 6.3

Diagram 6.4

NOTE:
PILOT SHIELD
REMOVED FOR
CLARITY

SPARK GAP
2 to 4mm

10 to 20mm FLAME LENGTH

4138

VIEWING

WINDOW

SECURING
SCREW (4)

4146

4139

the rating that the boiler is going to be set to, for future reference.
The arrow is in the loose items pack.

Loosen the main burner pressure test point screw and connect
a suitable pressure gauge, see diagram 6.2.

Make sure that any remote controls are calling for heat.

Switch on/connect the electrical supply to the boiler and heating
system, neon 1 will light.

6.4 Testing - Electrical

Turn the boiler thermostat knob fully clockwise to the maximum
setting, which is about 82

o

C (180

o

F), neon 2 will light.

The lighting sequence is automatic as follows:-

The fan operates
The spark ignition operates
The pilot solenoid opens
The pilot burner lights

The ignition spark stops
The main solenoid opens

and after a short period of time the main burner will light, look
through viewing window, see diagram 6.3.

Very cold weather may delay the operating sequence.

The main burner will stay alight until switched off, either by the
control thermostat or a remote system control.

To make sure that the flame supervision device is working
correctly the following should be done.

1. With the main burner alight, turn the gas service cock “Off”,
see diagram 6.1.

After a short period the main burner and pilot will go out.

2. The correct working of the flame supervision device is shown
by neon 4 going out within 10 seconds and the ignition starting
up.

Neons 1, 2 and 3 should stay alight.

3. If the above does not happen, refer to fault finding Section
9.1.

4. To carry on turn the gas service cock “On”, see diagram 6.1.

When the boiler switches “Off”, both the pilot and main burner
go out. The automatic lighting sequence will work again when
heat is required.

If an external control switches the boiler off, the pump will run on
for a predetermined time.

6.5 Testing - Gas

With the boiler on proceed as follows:-

The whole of the gas installation, including the meter, should be
inspected, tested for soundness and purged in accordance with
the current issue of BS6891 and in IE the current edition of I.S.
813 "Domestic Gas Installations".

Check the main burner gas pressure at least 10 minutes after
the boiler has lit, refer to Data Label.

If necessary adjust the gas pressure to obtain the required
setting turning screw clockwise, to decrease pressure, see
diagram 6.2.

Should any doubt exist about the gas rate, check it using the gas
meter test dial and stop watch, at least 10 minutes after the
burner has lit, making sure that all other gas burning appliances
and pilot lights are off.

Turn the control thermostat knob fully anticlockwise to “Off”.
Remove the pressure gauge from the test point and refit screw,

neon 3 will light

neon 4 will light

making sure a gas tight seal is made.

When the control thermostat is turned to the “Off” position, by
hand, wait at least 30 seconds before turning “On” again.

There may be an initial smell given off from the boiler when new,
this is quite normal and it will disappear after a short period of
time.

Refit the electrical controls box, see diagram 5.8.

NOTE: The neon indicator lights on the printed circuit board are
an aid to fault finding, for details refer to Section 9.