2 flue and ventilation, 5 boilers in a compartment, 6 timber frame building – Glow-worm Ultimate 60BF User Manual

Page 8

Advertising
background image

8

221791B

2 Flue and Ventilation

2.5 Boilers in a Compartment

Where the installation of the boiler will be in an unusual position,
special requirements are needed, the current issue of BS6798
gives detailed guidance on these requirements.

A compartment used to enclose the boiler must be designed
and constructed specifically for this purpose. An existing
cupboard or compartment modified for the purpose may be
used. Details of essential requirements for cupboard or
compartment design are given in the current issue of BS6798.

The doorway opening should be of sufficient size to allow for
easy removal of the boiler.

Where the boiler is fitted in a cupboard or compartment,
permanent high and low level ventilation must be provided. The
minimum ventilation areas required are given in Table 3.

2.6 Timber Frame Building

If the boiler is to be installed in a timber frame building it should
be fitted in accordance with the Institute of Gas Engineers
document IGE/UP/7/1998. If in doubt seek advice from the local
gas undertaking or Hepworth Heating Ltd.

Diagram 2.1

A

DIRECTLY BELOW AN OPENABLE
WINDOW, AIR VENT, OR ANY OTHER
VENTILATION OPENING

300

B

BELOW GUTTER, DRIAN/SOIL PIPE

300

C

BELOW EAVES

300

D

BELOW A BALCONY OR CAR PORT

600

E

FROM VERTICAL DRAIN PIPES AND
SOIL PIPES

75

F

FROM INTERNAL OR EXTERNAL
CORNERS

250

G

ABOVE ADJACENT GROUND OR
BALCONY LEVEL

300

H

FROM A SURFACE FACING THE
TERMINAL

600

I

FACING TERMINALS

600

J

FROM OPENING (DOOR/WINDOW) IN
CAR PORT INTO DWELLING

1200

K

VERTICAL FROM A TERMINAL

1500

L

HORIZONTALLY FROM A TERMINAL

300

MINIMUM

POSITION

SPACING (mm)

MINIMUM SITING DIMENSIONS FORBALANCED FLUE
TERMINALS

3815A

Under Car Port etc.

H,I

J

D

F

K

A

A

F

G

E

A

G

G

B,C

B,C

F

F

K

K

K

C

L

L

G

G

FROM
OUTSIDE

COMPARTMENT AIR VENT TABLE

COMPARTMENT
VENTILATION
REQUIREMENTS

99cm

2

15in

2

99cm

2

15in

2

VENTILATION
FROM ROOM
OR SPACE

198cm

2

30in

2

198cm

2

30in

2

HIGH LEVEL

LOW LEVEL

VENT AREA

VENT AREA