Boiler connection, Air and flue pipe installation, Horizontal terminal installation – Glow-worm Ultracom cxi User Manual

Page 34: Vertical terminal installation, Horizontal pipes-completion of installation, Vertical pipes-completion of installation

Advertising
background image

34

10 Twin Flue - Length, Preparation and Installation

Diagram 10.27

13240

Boiler Connection

IMPORTANT: The flue seals are sensitive to mineral oil based

lubricants.

Do not grease the seals. If the seals do need to

be lubricated

use only water.

Place the twin flue adaptor onto the outlet of the boiler with

the air inlet to the left hand side, see diagram 10.27. Secure

the adaptor to the top panel with the screws provided. Care

should be taken when inserting the screw through the hole in

adaptor top.

To facilitate engagement, it is recommended that the rubber

‘O’ rings are lubricated with silicone grease or water prior to

assembly.

Air and Flue Pipe Installation

The air and flue pipes can now be built up from the boiler.

The flue must be designed with a continuous fall towards the

boiler. If using the horizontal flue pipe or 90° bends the pipe

must be inclined at 44mm/metre (2.5°)

minimum, see diagram

10.25.

Alternatively if space allows, use 45° bends in place of 90º

bends.

To avoid rain ingress to the air Inlet terminal, it is good

practice to aim the inlet downwards by approx 2° as rain can

damage the boiler. The Flue outlet pipe must always run at

44mm/metre (2.5°) back to the boiler.

IMPORTANT:

Long lengths of flues must be secured to the wall or ceiling it

runs against. Use at least one fixing bracket on each flue joint

used or on straight flue runs every joint and for every metre

flue run.

Provision must be made in concealed boxing or ductwork that

the flue joints can be inspected during annual servicing.

The flue seals are sensitive to mineral oil based lubricants.

Do

not grease the seals. If the seals do need to be lubricated

use only water.

Do not use the flue pipe to attach other pipes or equipment.

If visible, advise the householder not to hang or clip items to

flue pipes.

Do not stress the flue connections during the installation this

can damage the flue seals.

Horizontal Terminal Installation

NOTE: The air inlet terminal and the flue outlet terminals

must never be installed on the opposite sides of a property.

Termination must only be on the same wall or adjacent walls.

When installed close together separated vertically, the air

inlet must be fitted below the flue outlet terminal (see diagram

10.25).

The air terminal must not terminate less than 20mm from an

adjacent wall or structure and the flue outlet terminal less

than 100mm from any adjacent wall or structure. With due

consideration to terminal clearances mentioned in section 4.2

drill the one or two holes as required with a 90mm core drill.

Push the horizontal terminal through the wall allowing approx.

100mm to protrude outside.

Push a grey rubber wall seal onto either side of the wall

ensuring that both wall seals are pushed up to the wall

surface, see examples (b) and (c) diagram 10.25.

Vertical Terminal Installation

With due consideration to terminal clearances mentioned in

Section 4.2, project the rise of the flue pipe to roof level and

cut 150mm hole in the roof.

(a) Pitched Roof

Fit the required pitched roof weather collar over the 150mm

hole in the roof. Make good the tiling or slating around the

collar incorporating the flashing of the weather collar. Position

the angle cap over the weather collar in the correct orientation

to attain the correct angle for your roof. One way round gives

a pitch of 25°-38° and the other gives 37°- 50°.

(b) Flat Roof

Fit the aluminium weather collar over the 150mm hole in the

roof ensuring a weather tight seal.

Horizontal Pipes-Completion of Installation

Having built the pipe(s) from the boiler to the terminal(s), the

length of the final pipe piece can be determined. Cut pipes at

the opposite end to the ‘O’ ring seal making square and free

from burrs. Push the horizontal terminal through the wall to

engage the final pipe piece and pull back ensuring the grey

wall seals are fully pulled up to the outside and inside wall

faces.

Vertical Pipes-Completion of Installation

Refer to diagram 10.25.

For installation of (a), attach the twin pipe to concentric

flue adaptor, part number A2011600, to the base of vertical

terminal assembly. For installation of (b), attach the single

pipe to concentric adaptor, part number A2011500, to the base

of vertical terminal assembly.

With the vertical terminal assembly positioned in the roof,

the length of the final pipe can be determined. Cut the flue

to the desired length measuring from the ‘O’ ring seal end

and discard the plain end of the tube. The cut end should

be square and free from burrs. Carefully push the terminal

assembly upwards to allow room for fitting the final flue

piece(s). Fit a 100mm fixing bracket to the terminal assembly

Part No2000460486. Pull the terminal assembly down and

join to the flue system. Ensure that the terminal is making a

weather tight seal on the weather collar. Secure the fixing

bracket fitted to the terminal to the roofing struts or a purpose

made batton.

Advertising