15 replacement of parts, 19 domestic hot water thermistor, 20 automatic air vent – Glow-worm Ultracom cxi User Manual

Page 60: 21 low water pressure sensor

Advertising
background image

60

15 Replacement of Parts

15.19 Domestic Hot Water Thermistor

For access, refer to section 15.1.

Refer to diagram 15.14.

Disconnect the domestic hot water thermistor electrical

connections

Remove hot water thermistor and retaining clip.

Remove domestic hot water thermistor from clip.

NOTE: When reconnecting electrical connections, polarity is

not important.

Carry out a functional test of the controls.

15.20 Automatic Air Vent

For access, refer to section 15.1.

Drain the boiler heating circuit as described in the appropriate

section of 15.1.

Refer to diagram 15.15 and gain access through the plastic

maintenance cover.

Unscrew the automatic air vent.

Fit the new automatic air vent and ‘O’ ring ensuring the vent

cap is left loose.

Refill, vent and pressurise the boiler.

15.21 Low Water Pressure Sensor

For access, refer to section 15.1.

Drain the boiler heating circuit as described in the appropriate

section of 15.1.

Refer to diagram 15.16.

Disconnect the electrical lead.

Remove the retaining clip, remove the low water pressure

sensor.

Fit new ‘O’ ring.

Fit the new low water pressure sensor.

Refill vent and pressurise the boiler.

13258

Diagram 15.15

AUTOMATIC

AIR VENT

RETAINING

CLIP

MAINTENANCE

COVER

Diagram 15.14

13550

13315

Diagram 15.16

Advertising