09 ff, 18 fault finding – Glow-worm Xtramax User Manual

Page 31

Advertising
background image

31

4000116705-2

18 Fault Finding

WARNING. Always isolate the boiler from the electrical supply
before carrying out any electrical replacement work.

On completion of a fault finding task that has required the
disconnection and making of electrical connections, the check
for earth continuity, polarity and resistance to earth must be
carried out.

If any gas-carrying components are disturbed, removed or
replaced it will be necessary on completion to check for gas
soundness with leak detection fluid.

Before trying to operate the boiler make sure that :

• All gas supply cocks are open and that the gas supply has
been purged of air.

• The heating system pressure is at least 1 bar.

• There is a permanent mains supply to the boiler.

• The fuse on the PCB is intact.

Preliminary electrical system checks, as outlined in a multimeter
instruction book, are the first checks to be carried out during a
fault finding procedure.

Should there be any doubt about the voltage supply to any of the
components, it is possible to carry out a simple electrical test to
ensure all is operational in that area.

To carry out the electrical test, gain access to the main Printed
Circuit Board (PCB), as described previously, and measure the
voltages according to table 2.

Table 2

Voltage

Measured value

Measuring point

230 Volt

230 V AC

Between terminals H8.1 and H8.2

24 Volt

maximum 33V DC

Between terminals B2.4 and B2.7

15 Volt

15V

+ 0.5V

Between terminals B2.4 and B2.2

Display

5V

+ 0.5V

Between terminals B2.4 and B4.2

09

FF

Sec 052

A fault code is displayed on the left hand side of the LCD display, whilst at the same time, the letters appear with a
telephone symbol.

Thermistor values

The following table applies to the central heating, domestic hot
water and storage vessel thermistors:

Temperature (

°

C)

Resistance (

)

0

32565

5

25345

10

19875

15

15700

20

12500

25

10000

30

8060

35

6535

40

5330

45

4370

50

3605

55

2989

60

2490

65

2085

70

1755

75

1480

80

1260

85

1070

90

920

95

785

100

680

System pressure sensor

The resistance of the sensor at various pressures is as follows:

0 bar

between 280

and 320

1 bar

between 195

and 220

3 bar

between 93

and 143

The XTRAMAX has an on-board fault diagnostic
system. Should a fault occur on the boiler, the warning

LED at the top of the user display

will illuminate

and the LCD display will indicate the precise area
where the fault has occurred.

Advertising