Operation, Testing & maintenance, Ballast wiring block diagram 6. labels – IOTA I-40 User Manual
Page 3: Completing installation
Page 3
5. BALLAST WIRING BLOCK DIAGRAM
6. LABELS
Attach the appropriate labels adjacent to the
TBTS. Annotate Re-lamping label for lamp type and wattage. The
Caution and the Re-lamping labels must be on the fixture in a readily visible location to anyone attempting to ser-
vice the fixture.
7. COMPLETING INSTALLATION
When the installation is complete, switch the A.C. power on and join the
I-40 unit connector.
OPERATION
Normal Mode – A.C. power is present. The A.C. ballast operates the fluorescent lamp(s) as intended. The I-40 is in the
standby charging mode. The
TBTS will be lit providing a visual indication that the battery is being charged.
Emergency Mode – The A.C. power fails. The I-40 senses the A.C. power failure and automatically switches to the
Emergency Mode. One lamp is illuminated, at reduced output, for a minimum of 90 minutes. When the A.C. power is
restored, the
I-40 switches the system back to the Normal Mode and resumes battery charging. See page 1 of the
Instruction Manual.
TESTING & MAINTENANCE
Pressing the red lens on the
TBTS turns off the light on the TBTS and forces the unit into emergency mode, inter-
rupting power to the designated A.C. ballast. The emergency lamp is now being lit by the
I-40 unit. After releasing the
TBTS, the fixture returns to normal operation after a momentary delay. To simulate a “BLACK OUT” use the circuit
breaker to turn off A.C. power.
Initial Testing – Allow the unit to charge approximately 1 hour, then press the TBTS to conduct a short discharge test.
Allow a 24 hour charge before conducting a one hour test.
The
I-40 is a maintenance free unit, however, periodic inspection and testing is required. NFPA 101, Life Safety Code,
outlines the following schedule:
Monthly – Insure that the TBTS is illuminated. Conduct a 30 second discharge test by depressing the TBTS. One lamp
should operate at reduced output.
Annually – Insure that the TBTS is illuminated. Conduct a full 1
1
/
2
hour discharge test. The unit should operate as
intended for the duration of the test.
“Written records of testing shall be kept by the owner for inspection by the authority having jurisdiction.”
SERVICING SHOULD BE PERFORMED BY QUALIFIED PERSONNEL.
Consult Customer Service or visit www.iotaengineering.com for current warranty information.
BLACK
A.C. BALLAST
HOT A.C. LINE
WHT
WHITE
(120V) BLK
(277V) ORG
COMMON
Select proper voltage lead. Cap unused lead.
WHT/BLK
WHT/RED
WHT
(+) RED/BLK
OR
RED W/TAG
(+) RED
TBTS
BLACK
A.C. BALLAST
HOT A.C. LINE
WHT
WHITE
(120V) BLK
(277V) ORG
COMMON
Select proper voltage lead. Cap unused lead.
WHT/BLK
WALL SWITCH
WHT/RED
WHT
(+) RED/BLK
OR
RED W/TAG
(+) RED
TBTS
➀
➀
➀
➀
Illustration 3
Switched Fixture
Unswitched Fixture
I-40
I-40