IMPORTANT SAFEGUARDS

When using electrical equipment, basic safety precautions should always be followed, including the following:

READ AND FOLLOW ALL SAFETY INSTRUCTIONS

1.

CAUTION – To prevent electrical shock, do not mate unit connector until installation is complete and A.C. power

is supplied to the unit.

2.

CAUTION – This fixture provides more than one power supply output source. To reduce the risk of electrical

shock, disconnect both normal and emergency sources by turning off the A.C. branch circuit and by disconnect-

ing the unit connector.

3.

CAUTION – This is a sealed unit. The integral, high temperature Ni-Cad battery is not replaceable. Replace the

entire unit when necessary and recycle or dispose of the nickel-cadmium battery properly.

4.

DO NOT USE OUTDOORS. The I-880 is for use with grounded, UL Listed, indoor fixtures. Not for use in heated

air outlets or hazardous locations.

5. The

I-880 requires an unswitched A.C. power source of either 120 or 277 volts. Properly cap the unused A.C.

lead.

6. Do not mount near gas or electric heaters.
7. The

I-880 should be mounted in locations and at heights where it will not readily be subjected to tampering by

unauthorized personnel.

8. The

I-880 is suitable for mounting in the ballast compartment or on top of the fixture. For top mount, order op-

tional mounting kit TMK-80.

9. The

I-880 will cold strike and operate one 2

′–8′ or two 2′–4′ instant start, rapid start, U shape or circline, T8

through T12 fluorescent lamps, or one 2

′–4′ 28W or 54W HO or VHO fluorescent lamp, including energy saving

and long 4 pin compact lamps for 90 minutes.

10.

The

I-880 is compatible with most A.C. ballasts (including multiple lamp) as follows:

Magnetic ballasts – either one or two lamp emergency operation.

Electronic ballasts – one lamp emergency operation, consult Customer Service for two lamp emergency opera-

tion wiring diagrams.

11. The use of accessory equipment not recommended by the manufacturer may cause an unsafe condition.
12. Do not use this equipment for other than intended use.
13. Install in accordance with the National Electrical Code and local regulations.
14. Installation and servicing should be performed by qualified personnel.
15. Lighting fixture manufacturers, electricians, and end-users need to ensure product system compatibility

before final installation.

SAVE THESE INSTRUCTIONS

I-880

SERIES D

EMERGENCY

LIGHTING EQUIPMENT

INSTRUCTION MANUAL

THIS UNIT CONTAINS A

RECHARGEABLE NICKEL-

CADMIUM BATTERY. PLEASE

RECYCLE OR DISPOSE OF

PROPERLY.

P.O. BOX 11846 TUCSON, AZ 85734

(520) 294-3292 • FAX (520) 741-2837

www.iotaengineering.com

Advertising