Installation instructions, Lamps operated, Mounting the i-880 – IOTA I-880 User Manual

Page 2: Wiring, Installing the charge indicator, Illustration 1 recessed troffer fixture, Illustration 2 strip fixture

Advertising
background image

Page 2

7/8" BUSHING

FIXTURE

BALLAST CHANNEL COVER

PLASTIC TUBE

CHARGE INDICATOR
LIGHT

FIXTURE LENS

INSTALLATION INSTRUCTIONS

CAUTION: Before installing, make certain the A.C. power is off and the I-880 unit connector is disconnected.

1. LAMPS OPERATED

The

I-880 can be used with most

2

′–8′ lamps. Refer to the chart below for the type of lamp(s) operated and the number

of lamps to be operated in emergency mode.

*The 6

″ violet leads provide the lamp selection option. The unit is shipped from the factory with the leads disconnected

and capped. When used with particular lamp types, violet leads should be connected to one another. Refer to chart for

lamp selection options.

2. MOUNTING THE I-880

Remove the ballast channel cover. Mount the

I-880 in the ballast channel at least

1

/

2

″ away from the A.C. ballast(s).

The

I-880 may also be mounted on top of the fixture. The optional top mounting kit (Catalog No. TMK-80) may be

ordered separately from Customer Service.

When battery packs are remote mounted, consult Customer Service for the maximum allowable distance between

the battery pack and lamp.

3. WIRING

Refer to the wiring diagrams on the back page for the appropriate wiring of lamp(s) and ballast. Install in accordance

with the National Electrical Code and local regulations. For additional wiring diagrams consult Customer Service.

4. INSTALLING THE CHARGE INDICATOR

Recessed Troffer Fixture – Select a convenient location with proper clearance in the ballast cover and drill or

punch a

7

/

8

″ hole (

1

/

2

″ knockout). Insert the

7

/

8

″ bushing into the hole. Push the plastic tube through the bushing.

Disconnect the leads from the

LED housing and route the leads down the plastic tube. Reconnect the leads to the

housing, observing the proper polarity (Red/Black or Red lead w/connector to positive (+) red tab). Push the entire

assembly back into the tube until the lens collar rests against the plastic tube. The plastic tube should be adjusted

so that the

Charge Indicator is within ¼

″ of the fixture lens. The Charge Indicator must be visible after installa-

tion. Refer to Illustration 1.

Strip Fixture – Select a convenient location on the side of the fixture so the

Charge Indicator can be seen after

installation. Allow for proper clearance inside the fixture and drill or punch a

1

/

2

″ hole. Disconnect the leads from

the

LED housing. Push the LED housing into the

1

/

2

″ hole until it is firmly locked in place. Reconnect the leads,

observing proper polarity (Red/Black or Red lead w/connector to positive (+) red tab). Refer to Illustration 2.

Illustration 1 Recessed Troffer Fixture

FIXTURE

CHARGE

INDICATOR

LIGHT

(POS LEAD)
RED/BLK OR
RED W/CONNECTOR

WHITE/RED

LEAD

+ RED

Illustration 2 Strip Fixture

I-880

OBSERVE PROPER POLARITY

I-880

2 -4 T-8/T-12 Single & Bipin Pin

1

LAMP TYPE

OPTION

2

5 -8 T-8/T-12 Single & Bipin Pin

EMERGENCY

OPERATION

One Lamp

One Lamp

*VIOLET

LEADS

Connected

Disconnected

3

2 -4 T-8/T-12 Single & Bipin Pin

Two Lamp

Disconnected

4

2 -4 28W, 54W T5

One Lamp

Connected

Advertising