IOTA ISD-80 User Manual

Isd-80, Important safeguards, Instruction manual

Advertising
background image

IMPORTANT SAFEGUARDS

When using electrical equipment, basic safety precautions should always be followed, including the following:

READ AND FOLLOW ALL SAFETY INSTRUCTIONS

1.

CAUTION – To prevent electrical shock, do not mate unit connector until installation is complete and A.C. power

is supplied to the unit.

2.

CAUTION – This fixture provides more than one power supply output source. To reduce the risk of electrical

shock, disconnect both normal and emergency sources by turning off the A.C. branch circuit and by disconnect-

ing the unit connector.

3.

CAUTION – This is a sealed unit. The integral, high temperature Ni-Cad battery is not replaceable. Replace the

entire unit when necessary and recycle or dispose of the nickel-cadmium battery properly.

4.

DO NOT USE OUTDOORS. The ISD-80 is for use with grounded, UL Listed, damp location rated, indoor fix-

tures. Not for use in heated air outlets or hazardous locations.

5. The

ISD-80 requires an unswitched A.C. power source of 110-277V 50/60Hz.

6. Do not mount near gas or electric heaters.
7. The

ISD-80 should be mounted in locations and at heights where it will not readily be subjected to tampering by

unauthorized personnel.

8. The

ISD-80 is suitable for mounting in the ballast compartment or on top of the fixture. For top mount, order

optional mounting kit TMK-80.

9. The

ISD-80 will cold strike and operate one 14W to 54W T5 or 2

′–4′ instant start, rapid start, U shape or circline,

T8 through T12 fluorescent lamps, including energy saving and 4-pin long compact lamps for 90 minutes.

Not for use with single-pin lamps.

10.

The

ISD-80 is compatible with most A.C. ballasts (including multiple lamp) as follows:

Magnetic ballasts – one lamp emergency operation.

Electronic ballasts – one lamp emergency operation.

11.

ATTENTION - The ISD-80 utilizes filament heaters and an AC output circuit for wider compatibility of lamp types,

therefore

rapid start sockets only must be used for the emergency lamp application. The emergency lamp pins

must be wired independently to avoid shorting on the output circuit. Instant start sockets should not be used.

12. Suitable for use in damp locations and in enclosed and gasketed fixtures.
13. When used in conjunction with enclosed and gasketed fixtures, the

ISD-80 is suitable for mounting in the bal-

last compartment only.

14. For use in 0° C minimum, 50° C maximum ambient temperatures.
15. The use of accessory equipment not recommended by the manufacturer may cause an unsafe condition

, void

warranty, and result in non-compliance with UL specifications.

16. Do not use this equipment for other than intended use.
17. Install in accordance with the National Electrical Code and local regulations.
18. Installation and servicing should be performed by qualified personnel.
19. Lighting fixture manufacturers, electricians and end users need to ensure product system compatibility before

final installation.

SAVE THESE INSTRUCTIONS

ISD-80

SERIES AC

UNIVERSAL VOLTAGE

EMERgENCy

LIgHTINg EqUIpMENT

INSTRUCTION MANUAL

P.O. BOX 11846 TUCSON, AZ 85734

(520) 294-3292 • FAX (520) 741-2837

www.iotaengineering.com

Advertising