Installation instructions, Lamps operated, Mounting the isd-80 – IOTA ISD-80 User Manual

Page 2: Wiring

Advertising
background image

page 2

FIXTURE

LPTS

+ RED
LEAD

WHITE/RED

LEAD

+ RED

7/8" BUSHINg

FIXTURE

BALLAST CHANNEL COVER

pLASTIC TUBE

LpTS

FIXTURE LENS

INSTALLATION INSTRUCTIONS

CAUTION: Before installing, make certain the A.C. power is off and the ISD-80 unit connector is disconnected.

1. LAMpS OpERATED

The

ISD-80 can be used with most 2

′–4′ lamps 2-pin lamps. The ISD-80 is not for use with single-pin lamps. Refer

to the chart below for the type of lamp to be operated in emergency mode.

*The 6

″ violet leads provide the lamp selection option. The unit is shipped from the factory with the leads

disconnected and capped. When used with particular lamp types, violet leads should be connected to one anoth-
er. Refer to chart for lamp selection options.

2. MOUNTINg THE ISD-80

Remove the ballast channel cover. Mount the

ISD-80 in the ballast channel at least ½

″ away from the A.C. ballast.

The

ISD-80 may also be mounted on top of the fixture. The optional top mounting kit (Catalog No. TMK-80) may

be ordered separately from Customer Service.

When battery packs are remote mounted, consult Customer Service for the maximum allowable distance between

the battery pack and the lamp.

3. WIRINg

Refer to the wiring diagrams on the back page for the appropriate wiring of lamp(s) and ballast. Install in accordance

with the National Electrical Code and local regulations. For additional wiring diagrams consult Customer Service.

ATTENTION - The ISD-80 utilizes filament heaters and an AC output circuit for wider compatibility of lamp types,

therefore

rapid start sockets only must be used for the emergency lamp application. The emergency lamp pins

must be wired independently to avoid shorting on the output circuit. Instant start sockets should not be used.

4. INSTALLINg THE LIgHTED pUSH BUTTON TEST SWITCH (LpTS)

Recessed Troffer Fixture – Select a convenient location with proper clearance in the ballast cover and drill or

punch a

7

/

8

″ hole (½″ knockout). Insert the

7

/

8

″ bushing into the hole. push the plastic tube through the bushing.

Disconnect the leads from the

LPTS housing and route the leads down the plastic tube. Reconnect the leads to

the housing, observing the proper polarity (Red/Black or Red lead w/connector to positive (+) tab. The positive

terminal will be indicated by the red mark on the side of the

LPTS switch). push the entire assembly back into the

tube until the lens collar rests against the plastic tube. The plastic tube should be adjusted so that the

LPTS is within

¼

″ of the fixture lens. The LPTS must be visible after installation. Refer to Illustration 1.

Strip Fixture – Select a convenient location on the side of the fixture so the

LPTS can be seen after installa-

tion. Allow for proper clearance inside the fixture and drill or punch a ½

″ hole. Disconnect the leads from the LPTS

housing. push the

LPTS housing into the ½

″ hole until it is firmly locked in place. Reconnect the leads, observing

the proper polarity (Red/Black or Red lead w/connector to positive (+) tab. The positive terminal will be indicated

by the red mark on the side of the

LPTS switch). Refer to Illustration 2.

NOTE: For proper operation, use only the test accessories provided with the unit. See Page 1 of the Instruction

Manual.

Illustration 1 Recessed Troffer Fixture

Illustration 2 Strip Fixture

ISD-80

OBSERVE pROpER pOLARITy

ISD-80

(pOS LEAD)
RED/BLK
OR RED
W/CONNECTOR

p

OS

OPTION

LAMP TYPE

EMERGENCY

OPERATION

*VIOLET LEADS

1

2

3
4
5

2´-4´ T8/T12 Bipin

2´-4´ 14W-24W T5

22W T9, 9W T5 Circline

One Lamp

One Lamp
One Lamp

One Lamp

Connected

Connected

Connected

Disconnected

6

18W-36W Long Compact

One Lamp

Connected

2´-4´ 28W-54W T5

Disconnected

12W, 55W T5 Circline

One Lamp

40W-55W Long Compact

7

One Lamp

Disconnected