Installation instructions, Lamps operated, Mounting the i-48 – IOTA I-48 User Manual
Page 2: Wiring, Installing the threaded body test switch (tbts), Lamp type option, Emergency operation, Violet leads
Page 2
7/8" BUSHING
FIXTURE
BALLAST CHANNEL COVER
PLASTIC TUBE
TBTS
FIXTURE LENS
INSTALLATION INSTRUCTIONS
CAUTION: Before installing, make certain the A.C. power is off and the I-48 unit connector is disconnected.
1. LAMPS OPERATED
The
I-48 can be used with most
2
′–8′ lamps. Refer to the chart below for the type of lamp(s) operated and the number
of lamps to be operated in emergency mode. Contact Customer Service for answers about specific lamps.
*The
6
″ violet leads provide the lamp selection option. The unit is shipped from the factory with the leads
disconnected and capped. When used with particular lamp types, violet leads should be connected to one anoth-
er. Refer to chart for lamp selection options.
2. MOUNTING THE I-48
Remove the ballast channel cover. Mount the
I-48 in the ballast channel at least
1
/
2
″ away from the A.C. ballast(s).
When battery packs are remote mounted, consult Customer Service for the maximum allowable distance between
the battery pack and lamp.
3. WIRING
Refer to the wiring diagrams on the back page for the appropriate wiring of lamp(s) and ballast. Install in accordance
with the National Electrical Code and local regulations. For additional wiring diagrams consult Customer Service.
4. INSTALLING THE THREADED BODY TEST SWITCH (TBTS)
Recessed
Troffer
Fixture – Select a convenient location with proper clearance in the ballast cover and drill or
punch a
7
/
8
″ hole (
1
/
2
″ knockout). Insert the
7
/
8
″ bushing into the hole. Push the plastic tube through the bushing.
Route the leads of the
TBTS through the plastic tube. Connect the LED wires from the unit to the TBTS (Red/
Black or Red w/tag to Red, White/Red to White). Push the entire assembly back into the tube until the lens collar
rests against the plastic tube. The plastic tube should be adjusted so that the
TBTS is within ¼
″ of the fixture lens.
The
TBTS must be visible after installation. Refer to Illustration 1.
Strip Fixture – Select a convenient location on the fixture so the
TBTS can be seen after installation. Allow for
proper clearance inside the fixture and drill or punch a
1
/
2
″ hole. Remove the nut from the TBTS. Push the TBTS
housing into the
1
/
2
″ hole and secure with the nut. Connect the LED wires from the unit to the TBTS (Red/Black or
Red w/tag to Red, White/Red to White). Refer to Illustration 2.
Illustration 1 Recessed Troffer Fixture
FIXTURE
TBTS
+ RED
LEAD
WHITE
LEAD
Illustration 2 Strip Fixture
I-48
OBSERVE PROPER POLARITY
2
′-4′ T-8/T-12 Single & Bipin Pin
1
LAMP TYPE
OPTION
2
5
′-8′ T-8/T-12 Single & Bipin Pin
EMERGENCY
OPERATION
One Lamp
One Lamp
*VIOLET
LEADS
Connected
Disconnected
3
2
′-4′ T-8/T-12 Single & Bipin Pin
Two Lamp
Disconnected
I-48