Installation instructions, Lamps operated, Mounting the i-160r – IOTA I-160-R User Manual

Page 2: Wiring, Illustration 1 ceiling grid installation, Page 2

Advertising
background image

Page 2

INSTALLATION INSTRUCTIONS

CAUTION: Before installing, make certain the A.C. power is off and the I-160R unit connector is disconnected.

1. LAmPS OPERATED

The

I-160R can be used with most 2

′–8′ T8, 2′–4′ T5, or 4-pin compact lamps. Refer to the chart for the type of lamp(s) oper-

ated and the number of lamps to be operated in emergency mode. Contact Customer Service with questions about specific
lamps.

*The lamp selector leads each have a 3 position shorting P-nut connector. Select the proper wire combination from the chart

for the desired lamp(s) used. Cut and strip one of the selected wires (

3

/

8

″) and plug it into the P-nut of the second wire.

2. mOUNTINg ThE I-160R

Cut a 2

5

/

8

″ section from one side of the ceiling tile. Install the unit as shown in Illustration 1. Extend the flex conduit to a conve-

nient location on top of the fixture and punch a

7

/

8

″ hole. Feed the wires and flex connector through the hole in the fixture and

secure in place with the flex connector nut.

When battery packs are remote mounted, consult Customer Service for the maximum allowable distance between the battery

pack and the lamps.

CAUTION: Properly secure the I-160R in the ceiling grid to insure compliance with local, state, and federal guidelines

regarding ceiling mounted equipment.

3. WIRINg

Refer to the wiring diagrams on the back page for the appropriate wiring of lamp(s) and ballast. Install in accordance with the

National Electrical Code and local regulations. For additional wiring diagrams consult Customer Service.

OPTION

LAmP TyPE

EmERgENCy

OPERATION

*LAmP SELECTOR LEADS

Brn/Wht

Brown

Violet

32 Watt 4-ft. T8

One Lamp

59 Watt 8-ft. T8

One Lamp

95 Watt 8-ft. T12

One Lamp

70W Compact

42W Compact

One Lamp

17 Watt 2-ft. T8

Two Lamps

One Lamp

32W Compact

One Lamp

1
2
3
4
5
6
7

28W 4-ft. T5

18W Compact

26W Compact

18W Compact

54W 4-ft. T5

47W 4-ft. T5

39W 3-ft. T5

24W 2-ft. T5

95W 4-ft. T5

8
9

10
11
12
13
14
15
16

Two Lamps

Two Lamps

One Lamp
One Lamp
One Lamp
One Lamp
One Lamp
One Lamp

One Lamp

17 Watt 2-ft. T8

One Lamp

26W Compact

One Lamp

17
18

50W Long Compact

30W Long Compact

One Lamp

One Lamp

25W Long Compact

One Lamp

19
20
21

Illustration 1 CEILING GRID INSTALLATION

CHARGE

TEST

CEILING TILE

REFER TO THE WIRING
DIAGRAMS ON THE
BACK PAGE OF THE
INSTRUCTION MANUAL
FOR THE PROPER
WIRE DIAGRAM.

FLEX

TEST SWITCH
CHARGE LIGHT

WIRING HARNESS

SIDE VIEW

BOTTOM VIEW

I-160R