Operation, Testing & maintenance, Labels – IOTA I-162 User Manual

Page 3: Completing installation, Illustration 2, I-162, Page 3, B. unswitched fixture, C. switched fixture

Advertising
background image

Page 3

6. LABELS

Attach the appropriate labels adjacent to the

Test Switch and Charge Indicator. Annotate Re-lamping label for lamp

type and wattage. The Caution and the Re-lamping labels must be on the fixture in a readily visible location to anyone attempt-
ing to service the fixture.

7. COmPLETINg INSTALLATION

When the installation is complete, switch the A.C. power on and join the

I-162 unit connector.

Illustration 2

OPERATION

Normal Mode – A.C. power is present. The A.C. ballast operates the fluorescent lamp(s) as intended. The I-162 is in the standby

charging mode. The

Charge Indicator will be lit providing a visual indication that the battery is being charged.

Emergency Mode – The A.C. power fails. The I-162 senses the A.C. power failure and automatically switches to the Emergency

Mode. One or two lamps are illuminated, at reduced output, for a minimum of 90 minutes. When the A.C. power is restored, the

I-162 switches the system back to the Normal Mode and resumes battery charging. See page 1 of the Instruction manual.

TESTING & MAINTENANCE

Initial Testing – Allow the unit to charge approximately 1 hour, then conduct a short discharge test. Allow a 24 hour charge before

conducting a one hour test.
The

I-162 is a maintenance free unit, however, periodic inspection and testing is required. NFPA 101, Life Safety Code, outlines the

following schedule:
Monthly – Insure that the Charge Indicator light is illuminated. Conduct a 30 second discharge test by depressing the Test Switch.

One lamp or two lamps should operate at full or reduced output, depending on your configuration.
Annually – Insure that the Charge Indicator light is illuminated. Conduct a full 1

1

/

2

hour discharge test. The unit should operate as

intended for the duration of the test.

“Written records of testing shall be kept by the owner for inspection by the authority having jurisdiction.”

SERVICING SHOULD BE PERFORMED BY QUALIFIED PERSONNEL.

Consult Customer Service or visit www.iotaengineering.com for current warranty information.

SEPARATE
BRANCH
CIRCUIT:

BLACK

A.C. BALLAST

HOT A.C. LINE

WHITE

WHITE

(120V) BLK

(277V) ORG

TEST SWITCH

COMMON

BLK/ORG

BLK/ORG

BLACK

A.C. BALLAST

HOT A.C. LINE

WHITE

WHITE

(120V) BLK

(277V) ORG

TEST SWITCH

COMMON

Select proper voltage lead. Cap unused lead.

BLK/ORG

BLK/ORG

WALL

SWITCH

1

2

2

Use either BLK/ORG lead for wiring to common.

2

1

Select proper voltage lead. Cap unused lead.
Use either BLK/ORG lead for wiring to common.

2

1

1

2

2

B. Unswitched Fixture

I-162

I-162

BLACK

A.C. BALLAST

EM CIRCUIT

HOT

WHT

WHITE

(120V) BLK

(277V) ORG

TEST SWITCH

BLK/ORG

EM CIRCUIT

COMMON

BLK/ORG

AC BALLAST

CIRCUIT

HOT

COMMON

Select proper voltage lead. Cap unused lead.
Use either BLK/ORG lead for wiring to common.

1
2

1

2
2

BLACK

A.C. BALLAST

EM CIRCUIT

HOT

WHT

WHITE

(120V) BLK

(277V) ORG

TEST SWITCH

Select proper voltage lead. Cap unused lead.

BLK/ORG

EM CIRCUIT

COMMON

BLK/ORG

AC BALLAST

CIRCUIT

HOT

COMMON

WALL SWITCH

Use either BLK/ORG lead for wiring to common.

1

1

2

2
2

C. Switched Fixture

I-162

I-162

D. Unswitched Fixture

A. Switched Fixture

SAME
BRANCH
CIRCUIT:

Select proper voltage
lead. Cap unused lead.

Use either BLK/ORg
lead for wiring to
common.

1

2

Select proper voltage
lead. Cap unused lead.

Use either BLK/ORg
lead for wiring to
common.

1

2

Advertising