Installation instructions, Lamps operated, Mounting the isl-28 – IOTA ISL-28 User Manual

Page 2: Wiring, Installing the charge indicator, Installing the test switch

Advertising
background image

Page 2

INSTALLATION INSTRUCTIONS

CAUTION: Before installing, make certain the A.C. power is off and the
ISL-28 unit connector is disconnected.

1. LAMPS OPERATED

The

ISL-28 can be used with most 2´-4´ lamps. Refer to the chart below for the types of lamp(s) operated and the

number of lamps to be operated in emergency mode.

*The 6

″ violet leads provide the lamp selection option. The unit is shipped from the factory with the leads disconnected

and capped. When used with particular lamp types, violet leads should be connected to one another. Refer to chart for

lamp selection options.

2. MOUNTING THE ISL-28

Remove the ballast channel cover. Mount the

ISL-28 in the ballast channel at least

1

/

2

″ away from the A.C. ballast(s).

When battery packs are remote mounted, consult Customer Service for the maximum allowable distance between

the battery pack and the lamp.

3. WIRING

Refer to the wiring diagrams on the back page for the appropriate wiring of lamp(s) and ballast. Install in accordance

with the National Electrical Code and local regulations. For additional wiring diagrams consult Customer Service.

4. INSTALLING THE CHARGE INDICATOR

Select a convenient location on the side of the fixture so the

Charge Indicator can be seen after installation. Al-

low for proper clearance inside the fixture and drill or punch a

1

/

2

″ hole. Snap the

1

/

2

″ white bushing into the hole.

Push the LED

housing into the bushing and secure it in place with the

5

/

8

″ black bushing (see Illustration 1). Con-

nect the LED red and white wires to the ballast LED marked wires.

5. INSTALLING THE TEST SWITCH

The

Test Switch should be mounted on the side of the fixture, preferably adjacent to the Charge Indicator. Drill

or punch a

1

/

2

″ mounting hole.

Illustration 1

OPTION

LAMP TYPE

EMERGENCY

OPERATION

*VIOLET LEADS

WIRING

DIAGRAMS

1

2

2 FT T5-T8 Single, Bipin

4 FT T5(28W) -T8

Single, Bipin

One Lamp

One Lamp

Connected

Disconnected

1, 2, 3, 4, 5, 6, 7, 8, 9

1, 2, 3, 4, 5, 6, 7, 8, 9

3

3 FT T5 Single, Bipin

One Lamp

Disconnected

1, 2, 3, 4, 5, 6, 7, 8, 9