Operation, Testing & maintenance, Ballast wiring block diagram 6. labels – IOTA ISL-540-35W User Manual

Page 3: Completing installation

Advertising
background image

Page 3

5. BALLAST WIRING BLOCK DIAGRAM

6. LABELS

Attach the appropriate labels adjacent to the

TBTS. Annotate Re-lamping label for lamp type and wattage. The

Caution and the Re-lamping labels must be on the fixture in a readily visible location to anyone attempting to ser-
vice the fixture.

7. COMPLETING INSTALLATION

When the installation is complete, switch the A.C. power on and join the

ISL-540 unit connector.

OPERATION

Normal Mode – A.C. power is present. The A.C. ballast operates the fluorescent lamp(s) as intended. The ISL-540 is in
the standby charging mode. The

TBTS will be lit providing a visual indication that the battery is being charged.

Emergency Mode – The A.C. power fails. The ISL-540 senses the A.C. power failure and automatically switches to the
Emergency Mode. One lamp is illuminated, at reduced output, for a minimum of 90 minutes. When the A.C. power is
restored, the

ISL-540 switches the system back to the Normal Mode and resumes battery charging. See page 1 of the

Instruction Manual.

TESTING & MAINTENANCE

Pressing the red lens on the

TBTS turns off the light on the TBTS and forces the unit into emergency mode, inter-

rupting power to the designated A.C. ballast. The emergency lamp is now being lit by the

ISL-540 unit. After releasing

the

TBTS, the fixture returns to normal operation after a momentary delay. To simulate a “BLACK OUT” use the circuit

breaker to turn off A.C. power.

Initial Testing – Allow the unit to charge approximately 1 hour, then press the TBTS to conduct a short discharge test.
Allow a 24 hour charge before conducting a one hour test.

The

ISL-540 is a maintenance free unit, however, periodic inspection and testing is required. NFPA 101, Life Safety

Code, outlines the following schedule:

Monthly – Insure that the TBTS is illuminated. Conduct a 30 second discharge test by depressing the TBTS. One lamp
should operate at reduced output.

Annually – Insure that the TBTS is illuminated. Conduct a full 1

1

/

2

hour discharge test. The unit should operate as

intended for the duration of the test.

“Written records of testing shall be kept by the owner for inspection by the authority having jurisdiction.”

SERVICING SHOULD BE PERFORMED BY QUALIFIED PERSONNEL.

Consult Customer Service or visit www.iotaengineering.com for current warranty information.

BLACK

A.C. BALLAST

HOT A.C. LINE

WHT

WHITE

(120V) BLK

(277V) ORG

COMMON

Select proper voltage lead. Cap unused lead.

WHT/BLK

WHT/RED

WHT

(+) RED/BLK

OR

RED W/TAG

(+) RED

TBTS

BLACK

A.C. BALLAST

HOT A.C. LINE

WHT

WHITE

(120V) BLK

(277V) ORG

COMMON

Select proper voltage lead. Cap unused lead.

WHT/BLK

WALL SWITCH

WHT/RED

WHT

(+) RED/BLK

OR

RED W/TAG

(+) RED

TBTS

Illustration 3

Switched Fixture

Unswitched Fixture

ISL-540

ISL-540