Page 2

INSTALLATION INSTRUCTIONS

CAUTION: Before installing, make certain the A.C. power is off and the
I-42-EM-B unit connector is disconnected.

Illustration 1 - Twin Lamp Fixture

INSURE WIRING IS IN ACCORDANCE WITH THE NATIONAL ELECTRICAL CODE AND LOCAL REGULATIONS.

1. LAMPS OPERATED

Refer to the chart for the type of lamp(s) operated and the number

of lamps to be operated in the emergency mode.
If you have any questions regarding specific lamps, contact
Customer Service.

The

6

″ violet leads provide the lamp selection option. The unit

is shipped from the factory with the leads disconnected and
capped. When used with particular lamp types, violet leads
should be connected to one another. Refer to the chart for
lamp selection options.

LPTS

A.C. BALLAST

CHANNEL

CEILING TILE

A.C. BALLAST

COMPARTMENT

LPTS

TMK-80

Illustration 2 - Top Mounting with TMK-80 Option

TBTS

TBTS

N

O

I

T

P

O

P

M

A

L

E

P

Y

T

Y

C

N

E

G

R

E

M

E

N

O

I

T

A

R

E

P

O

T

E

L

O

I

V

S

D

A

E

L

1

2

3

4

10W-18W

26W-42W

18W

One Lamp

One Lamp

Two Lamp

Two Lamp

Compact

Compact

Compact

Compact

Connected

Disconnected

Connected

Disconnected

10W-13W

5

6

7

18W

24W

36W

Long

Compact

Long

Compact

Long

Compact

One Lamp

One Lamp

One Lamp

Connected

Disconnected

Disconnected

2. MOUNTING THE I-42-EM-B

Mount

the

I-42-EM-B in the ballast channel or enclosed wireway so the wire leads are not exposed, at least ½

away from the A.C. ballast(s). Refer to Illustration 1. For mounting the

I-42-EM-B on top of the fixture, use the

optional TMK-80 mounting accessory for covering the wires that enter the fixture. Refer to Illustration 2.

When battery packs are remote mounted, consult Customer Service for the maximum allowable distance between

the battery pack and the lamp(s).

3. INSTALLING THE THREADED BODY TEST SWITCH (TBTS)

Select a convenient location on the side of the fixture so that the

TBTS can be seen after installation. Allow for

proper clearance and drill or punch a ½

″ hole. Remove the nut from the TBTS. Push the TBTS housing into the

½

″ hole and secure with the nut. Connect the LED wires from the unit to the TBTS (Red/Black or Red w/tag to

Red, and White/Red to White).

4. WIRING

A. When the

I-42-EM-B is installed on the same branch circuit, refer to Illustration 3, Figures A and B for

input wiring. When installed on separate branch circuits, refer to Illustration 3, Figures C and D for input wiring.
Per NEC, the

I-42-EM-B and A.C. ballast must be on the same panel board.

B. The

I-42-EM-B requires an unswitched A.C. power source of either 120 or 277 volts; therefore, when

used with switched fixtures, the

I-42-EM-B input must be wired ahead of the switch. Refer to Illustration 3

for switched and unswitched fixture wiring diagrams.

C. Refer to the wiring diagrams on the back page for the proper wiring. For wiring diagrams of ballasts not shown,
consult our Customer Service.

5. LABELS

Attach the appropriate labels adjacent to the

TBTS. Annotate Re-lamping label for lamp type and wattage. The

Caution and the Re-lamping labels must be on the fixture in a readily visible location to anyone attempting to ser-
vice the fixture.