INSTALLATION INSTRUCTIONS

CAUTION: Before installing, make certain the A.C. power is off and the
I-42-EM-R-J unit connector is disconnected.

1. LAMPS OPERATED

Refer to the chart below for the type of lamp(s) operated and the number of lamps to be operated in the emergency mode.

If you have any questions regarding specific lamps, contact Customer Service.

INSURE WIRING IS IN ACCORDANCE WITH THE NATIONAL ELECTRICAL CODE AND LOCAL REGULATIONS.

N

O

I

T

P

O

P

M

A

L

E

P

y

T

y

C

N

E

g

R

E

M

E

N

O

I

T

A

R

E

P

O

T

E

L

O

I

V

S

D

A

E

L

1

2

3

4

10W-18W

26W-42W

18W

One Lamp

One Lamp

Two Lamp

Two Lamp

Compact

Compact

Compact

Compact

Connected

Disconnected

Connected

Disconnected

10W-13W

5

6

7

18W

24W

36W

Long

Compact

Long

Compact

Long

Compact

One Lamp

One Lamp

One Lamp

Connected

Disconnected

Disconnected

The

6

″ violet leads provide the lamp selection option. The unit is shipped from the factory with the leads discon-

nected and capped. When used with particular lamp types, violet leads should be connected to one another. Refer
to the chart for lamp selection options.

2. MOuNTINg ThE I-42-EM-R-J

When used with ceiling mounted downlight fixtures, the

I-42-EM-R-J should be mounted on the fixture above the

ceiling.

When battery packs are remote mounted, consult Customer Service for the maximum allowable distance between

the battery pack and the lamp(s).

3. MOuNTINg ThE ThREADED BODy TEST SWITCh (TBTS)

Select a convenient location on the side of the reflector so that the

TBTS can be seen after installation. Allow for

proper clearance and drill or punch a

7

/

8

″ hole (

1

/

2

″ knockout). Remove the knurled nut (provided) and push the

TBTS housing into the

1

/

2

″ hole. Secure the TBTS with the knurled nut. NOTE: For proper operation, use only the

test accessories provided with the unit. See Page 1 of the Instruction Manual.

4. WIRINg

A.

When

the

I-42-EM-R-J is installed on the same branch circuit, refer to Illustration 1, Figures A and B for

input wiring. When installed on separate branch circuits, refer to Illustration 1, Figures C and D for input wiring.
Per NEC, the

I-42-EM-R-J and A.C. ballast must be on the same panel board.

B. The

I-42-EM-R-J requires an unswitched A.C. power source of either 120 or 277 volts; therefore, when

used with switched fixtures, the

I-42-EM-R-J input must be wired ahead of the switch. Refer to Illustration 1

for switched and unswitched fixture wiring diagrams.
C. Refer to the wiring diagrams on the back page for the proper wiring. For wiring diagrams of ballasts not shown,
consult our Customer Service.

5. LABELS

Attach the appropriate labels adjacent to the

TBTS. Annotate Re-lamping label for lamp type and wattage. The

Caution and the Re-lamping labels must be on the fixture in a readily visible location to anyone attempting to ser-

vice the fixture.

6. COMPLETINg INSTALLATION

When the installation is complete, switch the A.C. power on and join the

I-42-EM-R-J unit connector.