Installation instructions, Mounting the i-420-em-a, Mounting the threaded body test switch (tbts) – IOTA I-420-EM-A User Manual

Page 2: Wiring, Labels, Completing installation, Lamps operated, Illustration 1 downlight fixture

Advertising
background image

Page 2

Illustration 1 Downlight Fixture

FLEX “A”

JUNCTION

BOX

CEILING

TILE

A.C. BALLAST &

LAMP SOCKET COMPARTMENT

FLEX “B”

SWITCH BOX

TEST SWITCH

CHARGE LIGHT

I-420-EM-A

TBTS

2. MOUNTING THE I-420-EM-A

When used with ceiling mounted downlight fixtures, the

I-420-EM-A should be mounted on the fixture above the

ceiling. The flex conduit marked “A” should be wired into the ballast/lamp compartment or to an electrical junction

box on the fixture which allows access to the ballast/lamp connections. Refer to Illustration 1 for typical mounting.

When battery packs are remote mounted, consult Customer Service for the maximum allowable distance between

the battery pack and the lamp.

3. MOUNTING THE THREADED BODY TEST SWITCH (TBTS)

Cut a single gang switch box into the ceiling tile adjacent to the fixture within reach of the

I-420-EM-A flex

marked “B”. After mounting the switch box, connect flex “B” to the box and route all leads inside the box. Refer to

Illustration 1 for typical mounting.

4. WIRING

A.

When

the

I-420-EM-A is installed on the same branch circuit, refer to Illustration 2, Figures A and B for input

wiring. When installed on separate branch circuits, refer to Illustration 2, Figures C and D for input wiring. Per
NEC, the

I-420-EM-A and A.C. ballast must be on the same panel board.

B. The

I-420-EM-A requires an unswitched A.C. power source of either 120 or 277 volts; therefore, when used

with switched fixtures, the

I-420-EM-A input must be wired ahead of the switch. Refer to Illustration 2 for

switched and unswitched fixture wiring diagrams.

C. Refer to the wiring diagrams on the back page for the proper wiring. For wiring diagrams of ballasts not shown,

consult our Customer Service.

5. LABELS

Attach the appropriate labels adjacent to the

TBTS. Annotate Re-lamping label for lamp type and wattage. The

Caution and the Re-lamping labels must be on the fixture in a readily visible location to anyone attempting to ser-

vice the fixture.

6. COMPLETING INSTALLATION

When the installation is complete, switch the A.C. power on and join the

I-420-EM-A unit connector.

INSTALLATION INSTRUCTIONS

CAUTION: Before installing, make certain the A.C. power is off and the I-420-EM-A unit
connector is disconnected.

INSURE WIRING IS IN ACCORDANCE WITH THE NATIONAL ELECTRICAL CODE AND LOCAL REGULATIONS.

N

O

I

T

P

O

P

M

A

L

E

P

Y

T

Y

C

N

E

G

R

E

M

E

N

O

I

T

A

R

E

P

O

T

E

L

O

I

V

S

D

A

E

L

1

2

3

10W-32W

42W-57W

One Lamp

One Lamp

Two Lamp

Compact

Compact

Compact

Connected

Disconnected

Connected

10W-18W

4

5

6

18W

24W

36W

Long

Compact

Long

Compact

Long

Compact

One Lamp

One Lamp

One Lamp

Connected

Connected

Connected

Compact

Two Lamp

Disconnected

26W

7

1. LAMPS OPERATED

Refer to the chart for the type of lamp(s) operated and the number

of lamps to be operated in the emergency mode.If you have any
questions regarding specific lamps, contact Customer Service.

The

6

″ violet leads provide the lamp selection option. The unit

is shipped from the factory with the leads disconnected and
capped. When used with particular lamp types, violet leads
should be connected to one another. Refer to the chart for
lamp selection options.

Advertising