Operation, Testing & maintenance, Installing the charge indicator – IOTA I-13-L User Manual

Page 3: Installing the test switch, Labels, Completing installation

Advertising
background image

Page 3

3. INSTALLINg ThE ChARgE INDICATOR

Select a convenient location on the fixture so that the

Charge Indicator can be seen after installation. Allow for

proper clearance and drill or punch a

1

/

2

″ mounting hole. Disconnect the leads from the Charge Indicator. Push

the

Charge Indicator into the

1

/

2

″ hole until it is firmly locked into place. Reconnect the leads, observing proper

polarity (red lead to + red tab). Make certain all leads are enclosed in an appropriate wireway.

4. INSTALLINg ThE TEST SWITCh

The

Test Switch should be mounted on the fixture to allow access to authorized personnel. Drill or punch a

1

/

2

mounting hole. Make certain all leads are enclosed in an appropriate wireway.

NOTE: To ensure proper operation, use only the test accessories provided with the unit. See Page 1 of the Instruc-

tion Manual.

5. LABELS

Attach the appropriate labels adjacent to the

Test Switch and Charge Indicator. Annotate Re-lamping label for

lamp type and wattage. The Caution and the Re-lamping labels must be on the fixture in a readily visible location
to anyone attempting to service the fixture.

6. COMPLETINg INSTALLATION

A. When the installation is complete, switch the A.C. power on and join the

I-13-L unit connector.

B. Replace the ballast cover, fixture lens and other fixture hardware.

OPERATION

General – This unit is primarily designed to be used with compact fluorescent lamp downlight fixtures. It will wire in
conjunction with the existing A.C. ballast(s) and lamp(s) to provide the emergency function. It can also be wired for
emergency only operation.

Normal Mode – A.C. power is present. The A.C. ballast operates the fluorescent lamp(s) as intended. The I-13-L is in the
standby charging mode. The

Charge Indicator will be lit providing a visual indication that the battery is being charged.

Emergency Mode – The A.C. power fails. The I-13-L senses the A.C. power failure and automatically switches to the
Emergency Mode. One lamp is illuminated, at reduced output, for a minimum of 90 minutes. When the A.C. power is
restored, the

I-13-L switches the system back to the Normal Mode and resumes battery charging. See page 1 of the

Instruction Manual.

TESTING & MAINTENANCE

Initial Testing – Allow the unit to charge approximately 1 hour, then conduct a short discharge test by depressing the
Test Switch. The Charge Indicator light will go out and the fluorescent tube will be illuminated. When the I-13-L is
used in fixtures with more than one A.C. ballast, the second A.C. ballast is NOT de-energized with the

Test Switch. It

may, therefore, be advisable to switch the A.C. fixture power off prior to depressing the

Test Switch. Allow a 24 hour

charge before conducting a one hour test.

The

I-13-L is a maintenance free unit. however, periodic inspection and testing is required. NFPA 101, Life Safety Code,

outlines the following schedule:

Monthly – Insure that the Charge Indicator light is illuminated. Conduct a 30 second discharge test by depressing the
Test Switch. One lamp should operate at reduced output.

Annually – Insure that the Charge Indicator light is illuminated. Conduct a full 1

1

/

2

hour discharge test. The unit should

operate as intended for the duration of the test.

“Written records of testing shall be kept by the owner for inspection by the authority having jurisdiction.”

SERVICING SHOULD BE PERFORMED BY QUALIFIED PERSONNEL.

Advertising