Installation instructions, Mounting the isd-420-em-b, Wiring – IOTA ISD-420-EM-B User Manual

Page 2: Wiring the a.c. input, Lamps operated

Advertising
background image

page 2

*The 6

″ violet leads provide the lamp selection option. The unit is shipped from the factory with the leads

disconnected and capped. When used with particular lamp types, violet leads should be connected to one anoth-

er. Refer to chart for lamp selection options.

2. MOUNTINg THE ISD-420-EM-B

Mount

the

ISD-420-EM-B in the ballast channel or enclosed wireway so the wire leads are not exposed, at least

½

away from the A.C. ballast(s). Refer to Illustration 1. The

ISD-420-EM-B may also be mounted on top of the

fixture. The optional top mounting kit (Catalog No. TMK-80) may be ordered separately from Customer Service.

Refer to Illustration 2.

When battery packs are remote mounted, consult Customer Service for the maximum allowable distance between

the battery pack and the lamp.

3. WIRINg

Refer to the wiring diagrams on the back page for the appropriate wiring of lamp(s) and ballast. Install in accordance

with the National Electrical Code and local regulations. For additional wiring diagrams consult Customer Service.

4. INSTALLINg THE LIgHTED pUSH BUTTON TEST SWITCH (LpTS)

Select a convenient location on the side of the fixture so that the

LPTS can be seen after installation. Allow for

proper clearance and drill or punch a

7

/

8

″ (½″ knockout). push the LPTS housing into the ½″ hole. Connect the

leads, observing proper polarity (Red/Black or Red lead w/connector to positive (+) tab). The positive terminal will

be indicated by the red mark on the side of the LpTS switch. NOTE: For proper operation, use only the test acces-

sories provided with the unit. See Page 1 of the Instruction Manual.

5. WIRINg THE A.C. INpUT

A.

The

ISD-420-EM-B and A.C. ballast must be on the same branch circuit.

B.The

ISD-420-EM-B requires an unswitched A.C. power source of 110-277V 50/60HZ.

C.When the

ISD-420-EM-B is used with a switched fixture, the A.C. input to the ISD-420-EM-B must be connected

ahead of the fixture switch. Refer to Illustration 3 for switched and unswitched fixture wiring diagrams.

For 208VAC applications, consult Customer Service.

INSTALLATION INSTRUCTIONS

CAUTION: Before installing, make certain the A.C. power is off and the
ISD-420-EM-B unit connector is disconnected.

1. LAMpS OpERATED

Refer to the chart below for the type of lamp to be operated in the emergency mode.If you have any questions regard-

ing specific lamps, contact Customer Service.

Illustration 1: Twin Lamp Fixture

INSURE WIRING IS IN ACCORDANCE WITH THE NATIONAL ELECTRICAL CODE AND LOCAL REGULATIONS.

Illustration 2: Top Mount Option

LPTS

A.C. BALLAST

CHANNEL

CEILING TILE

A.C. BALLAST

COMPARTMENT

LPTS

TMK-80

ISD-420-EM-B

ISD-420-EM-B

OPTION

LAMP TYPE

EMERGENCY

OPERATION

*VIOLET LEADS

1

2

13W - 32W Compact

42W - 57W Compact

One Lamp

One Lamp

Connected

Disconnected