Installation instructions, Engineering considerations, Lamps operated – IOTA I-160-AC-L User Manual

Page 2: Mounting the i-160-ac-l, Wiring, Installing the charge indicator, Installing a test switch, Conditions of acceptability, Illustration 1 charge indicator light (led)

Advertising
background image

Page 2

INSTALLATION INSTRUCTIONS

CAUTION: Before installing, make certain the A.C. power is off and the I-160-AC-L unit connector is
disconnected.

1. LAmPS OPERATED

The

I-160-AC-L can be used with two (2) 42W compact fluorescent lamps. Contact Customer Service with questions about

specific lamps.

2. mOUNTINg ThE I-160-AC-L

mount the

I-160-AC-L in the ballast channel or enclosed wireway so the wire leads are not exposed, at least

1

/

2

″ away from the

A.C. ballast(s). The circuit board should be placed so that no live parts are accessible during routine maintenance or relamping.

The battery should be at least

1

/

2

″ from the A.C. ballast and other heat sources. Since heat rises, try to mount the battery as

low as possible.

CAUTION - Connect the battery to the unit before applying A.C. power.

3. WIRINg

Refer to the wiring diagram(s) on the back page for the appropriate wiring of lamp(s) and ballast. Install in accordance with the

National Electrical Code and local regulations. For additional wiring diagrams consult Customer Service.

4. INSTALLINg ThE ChARgE INDICATOR

Select a convenient location on the fixture so that the

Charge Indicator can be seen after installation. Allow for proper clear-

ance and drill or punch a

1

/

2

″ mounting hole. Disconnect the leads from the Charge Indicator. Push the Charge Indicator into

the

1

/

2

″ hole until it is firmly locked into place. Reconnect the leads, observing proper polarity (Red/Black or Red lead w/connec-

tor to positive (+) red tab). Refer to Illustration 1. make certain all leads are enclosed in an appropriate wireway.

NOTE: For proper operation, use only the test accessories provided with the unit. See Page 1 of the Instruction Manual.

5. INSTALLINg A TEST SWITCh

A test switch should be mounted on the ballast channel cover of a recessed troffer, or on the side of a strip fixture, preferable

adjacent to the charge indicator. Drill or punch a

1

/

2

″ mounting hole.

ENGINEERING CONSIDERATIONS

Use - For use only in complete equipment or final applications where the acceptability of the combination is determined
by Underwriters Laboratories, Inc.

These components have been judged on the basis of the required spacings in the Standard for Emergency Lighting
and Power Equipment UL 924, Sec. 29, which covers the end use product for which the component was designed.

CONDITIONS OF ACCEPTABILITy

1. Installed in a suitable ultimate enclosure.
2. Used with marked electrical rating.
3. Provide with proper spacing between live parts and enclosure and/or adjacent devices.
4. Factory wired only (terminations not suitable for field wiring).
5. Temperature tests may have to be repeated where battery temperature exceeds 61° C.
6. mounted within the end-use product such that the battery is secured and the test switch operates properly when
the end product is fully assembled.
7. End-use products employing one or more of these devices are to be marked in accordance with the Standard for
Emergency Lighting and Power Equipment, UL 924.

+ RED
LEAD

WHITE/RED

LEAD

+ RED

Illustration 1

Charge Indicator Light (LED)

(POS LEAD)
RED/BLK OR
RED W/CONNECTOR