Installation instructions, Fixture, Mounting the ilb – IOTA ILB-SL-CP12 User Manual

Page 2: Wiring, Installing the threaded body test switch (tbts), Illustration 1, Illustration 2

Advertising
background image

Page 2

INSTALLATION INSTRUCTIONS

CAUTION: Before installing, make certain the A.C. power is off and the ILB-SL-CP
unit connector is disconnected.

1. FIXTURE

The

ILB-SL-CP can be used with most LED loads that operate at 10-60 VDC. See the ILB Model Specification

Chart for output specifications of the unit being installed.

1. The ILB-SL-CP series has been evaluated to and found compliant to UL standard 924. The as-installed

performance of system must meet or exceed all Federal, State, and Local code requirements.

2. Refer to Addendum 11042014 for detailed specifications and methods to calculate emergency light levels.

2. MOUNTING THE ILB

Mount the

ILB-SL-CP in the driver/lamp compartment or enclosed wireway so the wire leads are not exposed, at

least ½

away from the driver. Refer to Illustration 1

and 2.

When battery packs are remote mounted, consult Customer Service for the maximum allowable distance between

the battery pack and the load.

3. WIRING

Refer to the wiring diagram on the back page for the appropriate wiring of the LED load and driver. Install in ac-

cordance with the National Electrical Code and local regulations. For additional wiring diagrams consult Cus-

tomer Service.

4. INSTALLING THE THREADED BODY TEST SWITCH (TBTS)

Recessed Troffer Fixture– Select a convenient location with proper clearance in the channel cover and drill or

punch a

7

/

8

″ hole (

1

/

2

″ knockout). Insert the

7

/

8

″ bushing into the hole. Push the plastic tube through the bushing.

Route the leads of the

TBTS through the plastic tube. Connect the LED wires from the unit to the TBTS (Red/

Black or Red w/tag to Red, White/Red to White). Push the entire assembly back into the tube until the lens collar

rests against the plastic tube. The plastic tube should be adjusted so that the

TBTS is within ¼

″ of the fixture lens.

The

TBTS must be visible after installation. Refer to Illustration 1.

Illustration 1

NOTE: Position the

TBTS so that

it can be seen after installation.

Illustration 2

+ RED
LEAD

WHITE

LEAD

FIXTURE

TBTS

7/8" BUSHING

FIXTURE

CHANNEL COVER

PLASTIC TUBE

TBTS

FIXTURE LENS

ILB-SL-CP

ILB-SL-CP

OBSERVE PROPER POLARITY

ILB-CP05

ILB-CP07

ILB-CP10

5 WATTS

7 WATTS

10 WATTS

ILB MODEL SPECIFICATION CHART

OUTPUT POWER (CONSTANT)

ILB-CP12

12 WATTS