Installation instructions, Led light, Mounting the ilb – IOTA ILB-2412 User Manual

Page 2: Wiring, Mounting the test accessories

Advertising
background image

Page 2

INSTALLATION INSTRUCTIONS

CAUTION: Before installing, make certain the A.C. power is off and the ILB unit
connector is disconnected.

1. LED LIghT

The

ILB can be used with most LED loads that operate at 24VDC or 12VDC. See ILB Model

Specification Chart for output specifications of the unit being installed.

2. mOUNTINg ThE ILB

The

ILB should be mounted on or nearby the fixture above the ceiling. The flex conduit marked “A” should be

wired into the driver/lamp compartment or to an electrical junction box on the fixture which allows access to the

fixture connections. Refer to Illustration 1 for typical mounting.

When battery packs are remote mounted, the remote distance can not exceed ½ of the distance from driver

to lamp specified by the A.C. driver manufacturer. Under no circumstances should the battery pack exceed a

distance of 50

′ from the lamp.

3. WIRINg

Refer to the wiring diagram on the back page for the appropriate wiring of the LED load and driver. Install in ac-

cordance with the National Electrical Code and local regulations. For additional wiring diagrams consult Cus-
tomer Service.

4. mOUNTINg ThE TEST ACCESSORIES

Cut a single gang switch box into the ceiling tile adjacent to the fixture within reach of the

ILB flex. After mounting

the switch box, connect flex to the box and route all leads inside the box. Note proper polarity of the charge indica-
tor light prior to removal from harness.

Illustration 1 Downlight Fixture

FLEX “A”

JUNCTION

BOX

CEILING

TILE

A.C. BALLAST &

LAMP SOCKET COMPARTMENT

FLEX “B”

SWITCH BOX

TEST SWITCH

CHARGE LIGHT

ILB

TEST

ACCESSORIES

LED FIXTURE

ILB-1207

ILB-1212

ILB-2407

ILB-2412

12VDC

12VDC

24VDC

24VDC

7

12

7

12

*ALL VOLTAgES AND WATTAgES ARE NOmINAL

ILB mODEL SPECIFICATION ChART

Advertising