Installation instructions, Led light, Mounting the ilb-1826 – IOTA ILB-1826 User Manual

Page 2: Wiring, Installing the charge indicator, Installing the test switch, Illustration 1: recessed troffer fixture, Illustration 2 : strip fixture

Advertising
background image

Page 2

INSTALLATION INSTRUCTIONS

CAUTION: Before installing, make certain the A.C. power is off and the
ILB-1826 unit connector is disconnected.

1. LED LIghT

The

ILB-1826 is designed for use with LED arrays that operate up to 24 Watts.

2. mOUNTINg ThE ILB-1826

Remove the ballast/driver channel cover. mount the

ILB-1826 in the ballast/driver channel at least ½

″ away from

the LED driver. The

ILB-1826 may also be mounted on top of the fixture. The optional top mounting kit (Catalog

No. TmK-32) may be ordered separately from Customer Service.

When the

ILB-1826 is remote mounted, consult Customer Service for the maximum allowable distance between

the

ILB-1826 and the LED load. The maximum allowable distance of the ILB-1826 battery from the ILB-1826

electronics is 2 feet.

NOTE: The ILB-1826 is suitable for use in cold-weather applications only when connected to a cold-weath-

er battery pack.

3. WIRINg

Refer to the wiring diagram on the back page for the appropriate wiring of the LED array and driver. Install in

accordance with the National Electrical Code and local regulations. For additional wiring diagrams consult Cus-

tomer Service.

4. INSTALLINg ThE ChARgE INDICATOR

Recessed Fixture – Select a convenient location with proper clearance in the ballast/driver channel or ac-

cess cover and drill or punch a

7

/

8

″ hole (½″ knockout). Insert the

7

/8

″ bushing into the hole. Push the plastic tube

through the bushing. Disconnect the leads from the

Charge Indicator housing and route the leads down the

plastic tube. Reconnect the leads to the housing, observing the proper polarity (Red/Black or Red lead w/connec-

tor to positive (+) red tab). Push the entire assembly back into the tube until the lens collar rests against the plastic

tube. The plastic tube should be adjusted so that the

Charge Indicator is within ¼

″ of the fixture lens. The Charge

Indicator must be visible after installation. Refer to Illustration 1.

Strip Fixture – Select a convenient location on the side of the fixture so the

Charge Indicator can be seen

after installation. Allow for proper clearance inside the fixture and drill or punch a ½

″ hole. Disconnect the leads

from the

Charge Indicator housing. Push the Charge Indicator housing into the ½

″ hole until it is firmly locked in

place. Reconnect the leads, observing proper polarity (Red/Black or Red lead w/connector to positive (+) red tab).

Refer to Illustration 2.

5. INSTALLINg ThE TEST SWITCh

The

Test Switch should be mounted on the ballast/driver channel cover of a recessed troffer, or on the side of a

strip fixture, preferably adjacent to the

Charge Indicator. Drill or punch a ½

″ mounting hole.

7/8" BUSHING

FIXTURE

BALLAST CHANNEL COVER

PLASTIC TUBE

CHARGE INDICATOR
LIGHT

FIXTURE LENS

Illustration 1: Recessed Troffer Fixture

FIXTURE

CHARGE

INDICATOR

LIGHT

+ RED/BLK
OR RED LEAD

WHITE/RED

LEAD

+ RED

Illustration 2 : Strip Fixture

ILB-1826

OBSERVE PROPER POLARITy

ILB-1826

BALLAST/DRIVER
ChANNEL COVER