Figure 1, Figure 2, Page 3 – IOTA IIS-350-UM User Manual

Page 3

Advertising
background image

Page 3

FIGURE 1 -

IIS-350-U WIRING CONNECTIONS FOR 120V LOAD

Consult the IIS-350-U

Application Notes for connecting the unit to specific lighting loads. Application Notes are

available on the internet or through Customer Service.

DO NOT ENERGIZE THE CIRCUIT AT THIS TIME.

CAUTION: Before proceeding to Wiring Step 3, make sure that all unused wires are properly capped.
Failure to do so may result in an unsafe condition and equipment failure.

3. INSTALLING THE BATTERY

A. Before installing the battery, check the torque on the hardware that connects the polarized connector to the
terminals as these connections may have loosened in transit and storage. The proper torques should be
70 in/lbs for a

Screw Stud terminal, and 65 in/lbs for an L Flag terminal.

B. Install the battery into the

IIS-350-U with the terminal posts facing toward the front of the unit. NOTE: The

IIS-350-U battery is heavy. To avoid injury, exercise caution when handling the battery.

C. Plug the battery connector together.

Note: Always apply proper torque to battery connections:

For Screw Stud batteries, initial torque is 70 in/lbs, annual is 65 in/lbs.

For L-Flag batteries, initial torque is 65 in/lbs, annual is 52 in/lbs.

NOTE: The emergency indicator lights will not illuminate at this time.

IIS_350_U-120V

INVERTER - UNINTERRUPTIBLE 120V

120V

UNSWITCHED

AC INPUT

CHARGER / INVERTER

WHT (NEUTRAL)

BLK (120V)

FLUORESCENT, INCANDESCENT, LED, HID

120V LIGHTING LOAD

GROUND

LUG

AC INPUT - CONNECT TO 120V AC INPUT ONLY

GROUND LUG - CONNECT FIXTURE SUPPLY

GROUND AND UNIT GROUND IN ACCORDANCE

WITH LOCAL CODE.

VIOLET
GRAY

OUTPUT LEADS

TEST SWITCH

INSTALL WIRES - DO NOT CONNECT INSTALL
WIRES UNTIL AFTER AC POWER IS SUPPLIED.

WHT/BLK

WHT/BLK

FIGURE 2 -

IIS-350-UM WIRING CONNECTIONS FOR 120V, 208V, 240V AND 277V LOADS

IIS_350_U_MULTI

INVERTER - UNINTERRUPTIBLE MULTI-TAP

120V

UNSWITCHED

AC INPUT

CHARGER / INVERTER

WHT (NEUTRAL)

BLK (120V)

FLUORESCENT, INCANDESCENT, LED, HID

LIGHTING LOAD

GROUND

LUG

AC INPUT -CONNECT TO 120V AC INPUT ONLY

GROUND WIRE - CONNECT FIXTURE SUPPLY

GROUND AND UNIT GROUND IN ACCORDANCE

WITH LOCAL AND NATIONAL CODES.

VIOLET

GRAY

OUTPUT LEADS

TEST SWITCH

120 TO 277V 350W

AUTOTRANSFORMER

GRAY

VIOLET (120V)

RED (208V)

BLUE (240V)

YELLOW (277V)

MULTI-TAP OUTPUT LEADS - SELECT THE PROPER

VOLTAGE AND CAP ALL UNUSED LEADS.

INSTALL WIRES - DO NOT CONNECT INSTALL WIRES
UNTIL AFTER AC POWER HAS BEEN SUPPLIED.

WHT/BLK

WHT/BLK

Advertising
This manual is related to the following products: