Installation instructions, Wiring, Mounting the iis-375-led – IOTA IIS-375-LED User Manual

Page 2

Advertising
background image

Page 2

2.

WIRING

1. CONNECTING THE NORMAL AC INPUT (FIGURE 1)
A.

For 120V supply, connect the AC line wire to the BLACK lead coming from the inverter housing labeled INPUT

WIRES.

For 277V supply, connect the AC line wire to the ORANGE lead coming from the inverter housing

labeled INPUT WIRES.

CAUTION: Cap the unused BLACK or ORANGE input wire. Failure to do

so may result in equipment failure and void the warranty.

B. Connect the Neutral wire to the WHITE lead labeled INPUT.

C. Connect the ground wire in accordance with local and national codes. A GREEN wire is provided for this pur-

pose.

Note: If the emergency fixtures are to be NORMALLY ON or SWITCHED, you may have to connect their flying

lead wires to these wires as well. Refer to

Figure 1 and STEP 2 below.

DO NOT ENERGIZE THE CIRCUIT AT THIS TIME.

2. CONNECTING REMOTE EMERGENCY FIXTURES (FIGURE 1)

A. Connect remote emergency fixtures to the correct output leads. The color code is as follows: neutral is GRAY,

120V is VIOLET, and 277V is YELLOW. All remote circuitry is to be wired in accordance with Article 700 of the
National Electric Code. Do not exceed the total rating of the

IIS-375-LED. When making connections to the

IIS-375-LED, DO NOT connect the Input Neutral (WHITE) to the Output Neutral (GRAY).

B. NORMALLY-OFF FIXTURES (only come on during power failure) - Connect the AC line input wire of the fixtures

to the appropriate output wires as above (120V or 277V). Connect the load neutral wire to the GRAY neutral
wire labeled OUTPUT. Refer to

Figure 1.

C. NORMALLY-ON FIXTURES - Follow Step 2B above. Then select the proper voltage flying lead from heatsink

assembly (BLACK for 120V, ORANGE for 277V) and connect to the unswitched AC input wires. Connect the
Neutral (WHITE) flying lead coming from the heatsink assembly to the unswitched AC input neutral of the sup-
ply line feeding the input wires. Refer to

Figure 1.

INSTALLATION INSTRUCTIONS

CAUTION: Before installing, make certain the A.C. power is off.

NOTE: The battery is shipped in separate packaging for ease of handling. Store the battery in a cool, dry and safe

location until ready for installation. The battery may be kept in storage for up to 3 months without recharging.

CAUTION: This is a dual input and output voltage unit. It can be connected to either a 120 or 277 volt supply.

The input and output voltages must match.

Not for use with HID Lighting.

1.

MOUNTING THE IIS-375-LED

1) Remove the front cover of the

IIS-375-LED by removing the two (2) screws located at the top of cover.

2) Knock out the keyhole slots at the rear of the unit and use for mounting the

IIS-375-LED securely to the wall.

There is an additional round hole for a #10 screw in the cabinet. Code requires that an additional screw be used
through this hole to prevent the unit from being inadvertently lifted up off the keyhole slots.

Do not drill any holes

in this unit. If a recessed junction box is to be mounted in the wall behind the unit, make sure an unswitched AC
supply of proper rated voltage is extended to the box, and that the remote wiring to the emergency fixtures is also
extended to the box prior to mounting the unit. A 1/2

″ conduit knockout is provided in the back of the unit for wires

to pass through. Sixteen inches of wire should be routed into the unit from the recessed junction box. NOTE: Input
and output wires must be run in separate conduits.

CAUTION: Do not drill holes into the cabinet; drill filings may

damage the unit and keep it from operating. If larger knockouts are required, use a chassis-punch through the ap-
propriate knockout to punch out a larger knockout.

3) If the wiring is to be external to the wall, extend both the unswitched supply, the normally-on lamp supply (if

used), and the load wires to the unit at this time.

CAUTION: The IIS-375-LED must be mounted securely. Do not rely on the junction box for supporting the
weight of the unit. Mount the IIS-375 securely to the wall using the keyhole slots provided.

ALWAYS CONSULT LOCAL CODES FOR STRUCTURAL REQUIREMENTS WHEN MOUNTING THE UNIT.