IOTA PE-BC Series User Manual

Important safeguards, Read and follow all safety instructions, Save these instructions installation manual

Advertising
background image

IMPORTANT SAFEGUARDS

When using electrical equipment, basic safety precautions should always be followed, including the following:

READ AND FOLLOW ALL SAFETY INSTRUCTIONS

1. Installation and servicing should be performed by qualified personnel.
2. Install in accordance with the National Electrical Code and local regulations.
3.

CAUTION – This fixture provides more than one power supply output source. To reduce the risk of electrical shock, disconnect

power by turning off the A.C. branch circuit and follow the installation instructions in their proper sequence as outlined.

4. Not for use in heated air outlets or hazardous locations.
5. Do not mount near gas or electric heaters.
6. This unit contains a high-temperature Ni-Cad battery. Recycle or dispose of the nickel cadmium battery properly when replac-

ing or removing this product.

7. The unit should be mounted in locations and at heights where it will not readily be subjected to tampering by unauthorized

personnel.

8. When using conduit, use flexible conduit only.
9. The use of accessory equipment not recommended by the manufacturer may cause an unsafe condition, void warranty, and

result in non-compliance with UL specifications.

10. Do not use this equipment for other than intended use.
11. This unit requires an unswitched A.C. power source of either 120 or 277 volts. Properly cap the unused A.C. lead.
12. Suitable for use in damp locations.

13. For use in 50° F minimum, 104° F maximum ( 10° - 40° C) ambient temperatures.
14. Allow battery 24 hours to charge before first use and 48 hours for remote capability battery charge.
15. Electricians and end-users need to ensure proper operation before final installation.

SAVE THESE INSTRUCTIONS

INSTALLATION MANUAL

COMBINATION EXIT SIGN / EMERGENCY LIGHT

MODELS

PERBC, PEGBC

PERBCR, PEGBCR

PERBCSD, PEGBCSD

PERBCRSD, PEGBCRSD

P.O. BOX 11846 TUCSON, AZ 85734

(520) 294-3292 • FAX (520) 741-2837

www.iotaengineering.com

1. Opening the Unit

The interior of the unit contains primary components and

hardware for completing installation. Using a slotted screw-
driver, gently pry off the front panel of the unit by inserting
the screwdriver into the slots. See

Fig. 1

2.

LED Emergency Light Assembly

Remove the LED emergency light module from the interior of

the unit. Remove the access knockout from the bottom of the
unit and route the emergency light connections through the
opening. Connect the wiring for the light module and attach
the light module by inserting the module into the housing slot
at a 20° angle and twisting into place. See

Fig 2.

NOTE: Assemble the LED Emergency Light onto the EXIT
housing before installation.

Fig. 1

Fig. 2

Advertising