IOTA EM1 Dual Head Emergency Fixture User Manual

Important safeguards, Read and follow all safety instructions, Save these instructions installation manual

Advertising
background image

IMPORTANT SAFEGUARDS

When using electrical equipment, basic safety precautions should always be followed, including the following:

READ AND FOLLOW ALL SAFETY INSTRUCTIONS

1. Installation and servicing should be performed by qualified personnel.
2. Install in accordance with the National Electrical Code and local regulations.
3.

CAUTION – This fixture provides more than one power supply output source. To reduce the risk of electrical shock, disconnect

power by turning off the A.C. branch circuit, and follow the installation instructions in their proper sequence as outlined.

4. Not for use in heated air outlets or hazardous locations.
5. Do not mount near gas or electric heaters.
6. This unit uses a sealed valve regulated lead acid battery. Batteries can be punctured if not handled properly, therefore use

caution when servicing. In the event battery acid comes in contact with eyes or skin, flush with fresh water and consult a phy-

sician immediately.

7. The unit should be mounted in locations and at heights where it will not readily be subjected to tampering by unauthorized

personnel.

8. When using conduit, use flexible conduit only.
9. The use of accessory equipment not recommended by the manufacturer may cause an unsafe condition, void warranty, and

result in non-compliance with UL specifications.

10. Do not use this equipment for other than intended use.
11. This unit requires an unswitched A.C. power source of either 120 or 277 volts. Properly cap the unused A.C. lead.
12. Suitable for use in damp locations.

13. For use in 50° F minimum, 104° F maximum ( 10° - 40° C) ambient temperatures.
14. Allow battery 24 hours to charge before first use.
15. Electricians and end-users need to ensure proper operation before final installation.

SAVE THESE INSTRUCTIONS

INSTALLATION MANUAL

FOR

EM1 AND EM1SD

DUAL-HEAD

LED EMERGENCY LIGHT

P.O. BOX 11846 TUCSON, AZ 85734

(520) 294-3292 • FAX (520) 741-2837

www.iotaengineering.com

THIS UNIT CONTAINS A

RECHARGEABLE VALVE-REGULATED

LEAD ACID BATTERY. PLEASE

RECYCLE OR DISPOSE OF

PROPERLY.

1. Mounting

For WALL MOUNTING, Remove the

mounting plate

from the fixture by pressing on the pressure pads on
the bottom of the unit. Remove the desired knockouts
on the back of the

mounting plate and push fixture

wires through the holes. After making electrical con-
nections, securely attach the mounting plate to the
J-box using the screws provided.

See Figure 1.

CAUTION: Before installing, make certain
the A.C. power is switched off at the circuit
breaker panel.

Fig. 1

Advertising