9. Operating voltage

10

PLM+ SERIES Quick Start Guide rev 1.0.0

9.1. Low voltage country considerations

Although the PLM+ Series has a wide range of operating mains voltage, some considerations can be applicable
for low voltage regions. PLM+ performs well throughout the specified nominal voltage range but has slightly better
efficiency at higher voltages. For regions with nominal voltage below 140 V, one could consider connecting the
amplifier in a three-phase delta or two phase split-phase configuration.

Note: Following connections applicable only for resulting voltage inside the amplifiers nominal
voltage range.

Connecting the amplifier in three phase delta configuration
In three-phase configuration where the phases are 120 degrees apart, one can connect three balanced loads in a
delta configuration. The connection is made between the phases instead of between the neutral and a phase.

Three phase delta configuration

Amp

120V

120V

120V

L1

Amp

L2

L3

Amp

N

N

Amp

Amp

Amp

3 phase Y 120V

3 phase delta 208V

208V

208V

208V

L1

L2

L3

Connecting the amplifier in a split phase configuration
In two phase split-phase configuration there are two phases separated by 180 degrees. Connecting between the
phases gives double the line voltage.

Two phase split-phase configuration

Split phase 100V

100V

100V

200V

L1

Amp

L2

N

Amp

Split phase 200V

L1

L2

N

Amp