4.4 The Tonnage Monitor Machine Settings Screen

Press the SELECT key to the right of the “Tonnage Monitor Machine Settings” in the Tonnage Monitor
Configuration screen as shown in Figure 16 to display the screen shown in Figure 17.

Stroke

Mode

Single Stroke

Drive

Speed

Stroke

Speed

SPM

SPM

0
0

Order

Counter

Current Status

Counter OFF

EXIT

0

0

Program/Run Switch

TOP

Tonnage
Monitor

Units:

Machine Rating:

Tons

4 Channel Tonnage Monitor General Settings

400.0

Machine Rating Alarm Level:

Max Forward Setpoint Level:

Max Reverse Setpoint Level:

Number of Data Windows:

Sample Window Start Angle:

Sample Window End Angle:

125 % of Mach. Rating
100 % of Mach. Rating

4

100.0°
260.0°

CHANGE
SETTING

Filter Frequency:

500 Hz

Auto-Zero Start Angle:

330.0°

Auto-Zero End Angle:

30.0°

Peak High Limit Stop Type:

Cycle Stop

DW High Limit Stop Type:

Top Stop

Auto Unbypass Leaving Setup Mode:

Yes

Bypass Low Limit in Setup Mode:

No

25 % of Mach. Rating

CLEAR
ALARM
COUNTERS

Stroke

Mode

Single Stroke

Drive

Speed

Stroke

Speed

SPM

SPM

0
0

Order

Counter

Current Status

Counter OFF

EXIT

0

0

Program/Run Switch

TOP

Tonnage
Monitor

Units:

Machine Rating:

Tons

4 Channel Tonnage Monitor General Settings

400.0

Machine Rating Alarm Level:

Max Forward Setpoint Level:

Max Reverse Setpoint Level:

Number of Data Windows:

Sample Window Start Angle:

Sample Window End Angle:

125 % of Mach. Rating
100 % of Mach. Rating

4

100.0°
260.0°

CHANGE
SETTING

Filter Frequency:

500 Hz

Auto-Zero Start Angle:

330.0°

Auto-Zero End Angle:

30.0°

Peak High Limit Stop Type:

Cycle Stop

DW High Limit Stop Type:

Top Stop

Auto Unbypass Leaving Setup Mode:

Yes

Bypass Low Limit in Setup Mode:

No

25 % of Mach. Rating

CLEAR
ALARM
COUNTERS

Figure 17: Tonnage Monitor Machine Settings Screen


The following sections describe the settings in this screen.

4.4.1 Units

This setting determines whether the tonnage monitor works in units of Tons or Metric Tons. This
setting can be changed at any time without recalibrating the tonnage monitor. All setpoints and other
tonnage related items will automatically change to the unit selected. For example, a press specified from
the manufacturer as a 400 metric ton press can have its machine rating entered while the units are set to
metric tons. However, the load cells available for calibrating the press display U.S. tons. Switch the
unit back to tons and the machine rating changes to 440.9. Now calibrate the press using U.S. tons.
After calibration, the units can be changed back to metric tons if desired.

NOTE:

Units can be changed at any time without messing up the calibration or the
setpoints. Everything will still work correctly including stored jobs.